EX2100 User’s Guide GEH-6632
Appendix B Ratings and Specifications
••••
B-3
Cabinet Dimensions & Weight
Redundant control with dual PCM
redundant converter in a three-cabinet
lineup
Width 141.74 in (3600 mm)
Height 104.32 in (2650 mm)
Depth 31.5 in (800 mm)
Weight of Converter cabinet
3,600 lbs.
Weight of Total Lineup (Converter,
Control, and Auxiliary cabinets)
5,600 lbs.
Cabinet type, control & auxiliary
NEMA 1 (IEC IP 20), convection cooled
Cabinet type, power conversion
NEMA 1 (IEC IP 20), forced air cooled
Power and Control Cable Access
Entrances from the top and/or bottom
Reliability
MTBF - Mean Time Between Failures
Simplex system 25,000 hrs
MTBF - Mean Time Between Failures
Redundant system 175,000 hrs
MTTR - Mean Time to Repair
Any subsystem 4 hrs
Acoustic
Generated Acoustic Noise (Preliminary)
PCM cabinet approximately 75 dB
Codes and Standards
UL 508C
Safety Standard Industrial Control Equipment
CSA 22.2 No. 14
Industrial Control Equipment
UL 796
Printed Wire Board Assemblies
ANSI IPC
Guidelines
IEC 801-2:1991
Electrostatic Discharge Susceptibility
ENV 50140:1993
Radiated RF Immunity
EN 50082-2:1994
Generic Immunity Industrial Environment
IEC 801-4
Electrical Fast Transient Susceptibility
IEC 1000-4-5
Surge Immunity
IEC 1000-4-6
Conducted RF Immunity
ENV 55011:1991
ISM Equipment Emissions
EN 61010-1
Safety of Electrical Equipment, Industrial Machines
IEC 529
Intrusion Protection Codes/NEMA 1/IP 20
IEEE 421.1
Standard Definitions for Excitation Systems for Synchronous machines
IEEE 421.2
Guide for Identification, Testing, and Evaluation of the Dynamic
Performance of Excitation Control Systems
IEEE 421.3
High-Potential Test Requirements for Excitation Systems
IEEE 421.4
Guide for the preparation of Excitation Systems Specs
IEEE 421.5
Recommended Practice for Excitation Systems for Power Stability
Studies
EN50178/LVD/EMC
CE Compliance
IEEE C57.12.01
General Requirements for Dry-Type Distribution & Power Transformers
IEEE C57.110
Recommended Practice for Establishing Transformer Capability when
supplying Non-Sinusoidal Load Currents
IEEE C57.116
IEEE Guide for Transformers Directly Connected to Generators
IEEE C37.90.1
Surge Withstand Capability (SWC) tests for Protective Relays and Relay
Systems
IEEE C57.18.10
Practices and Requirements for Semiconductor Power Rectifier
Transformers
Summary of Contents for EX2100
Page 1: ...g GE Industrial Systems GEH 6632 EX2100 Excitation Control User s Guide ...
Page 2: ......
Page 12: ...iv Contents GEH 6632 EX2100 User s Guide Notes ...
Page 44: ...2 24 Chapter 2 Functional Description GEH 6632 EX2100 User s Guide Notes ...
Page 56: ...3 12 Chapter 3 Printed Wiring Boards Overview GEH 6632 EX2100 User s Guide Notes ...
Page 92: ...5 16 Chapter 5 Diagnostic Interface Keypad GEH 6632 EX2100 User s Guide Notes ...
Page 98: ...A 6 Appendix A Warranty and Renewal Parts GEH 6632 EX2100 User s Guide Notes ...
Page 102: ...B 4 Appendix B Ratings and Specifications GEH 6632 EX2100 User s Guide Notes ...
Page 112: ...x Glossary of Terms GEH 6632 EX2100 User s Guide Notes ...
Page 117: ......
Page 118: ... QGXVWULDO 6 VWHPV HQHUDO OHFWULF RPSDQ 5RDQRNH OYG ZZZ LQGXVWULDO FRP 6DOHP 9 86 ...