9.3 Operating Environment
Temperature
Humidity
Altitude
Storage temperature
0
°
C~40
°
C
<95%
<1000m
-15
°
C~40
°
C
Note:
Output power is derated when UPS is above 1000m as following:
Altitude (M)
1000
1500
2000
2500
3000
3500
4000
4500
5000
Derating Power
100%
95%
91%
86%
82%
78%
74%
70%
67%