3.6 H-## High Perf Parameters
3.6.1 H-0# High Perf Operations
H-01 Option Detection
Option:
Function:
[0]
*
Protect
Option
Config.
Freezes the current settings and prevents
unwanted changes when missing or
defective options are detected.
[1]
Enable
Option
Change
Changes frequency converter settings and is
used when modifying the system configu-
ration. This parameter setting returns to
[0]
Protect Option Config.
after an option
change.
H-03 Restore Factory Settings
Option:
Function:
Use this parameter to specify normal operation,
to perform tests, or to restore all parameters
except:
•
•
•
.
This function is active only when the power is
cycled (power off/power on) to the frequency
converter.
[0]
*
Normal
operation
Normal operation of the frequency converter
with the motor in the selected application.
[2]
Restore
Factory
Settings
[2] Restore Factory Settings
Resets all parameter
values to default settings, except for:
•
•
•
.
The frequency converter resets during the next
power-up.
Parameter H-03 Restore Factory Settings
also
reverts to the default setting
[0] Normal
operation
.
H-04 Auto-Reset (Times)
Option:
Function:
Select the reset function after
tripping. Once reset, the frequency
converter can be restarted.
[0]
Manual reset
Select
[0] Manual reset
, to perform a
reset via [RESET] or via the digital
inputs.
[1]
Automatic reset x 1
Select
Automatic reset x 1…x20
[1]-
[12] to perform between one and
twenty automatic resets after
tripping.
H-04 Auto-Reset (Times)
Option:
Function:
[2]
Automatic reset x 2
[3]
Automatic reset x 3
[4]
Automatic reset x 4
[5]
Automatic reset x 5
[6]
Automatic reset x 6
[7]
Automatic reset x 7
[8]
Automatic reset x 8
[9]
Automatic reset x 9
[10]
Automatic reset x 10
[11]
Automatic reset x 15
[12]
Automatic reset x 20
[13]
*
Infinite auto reset
Select
[13] Infinite Automatic Reset
for continuous resetting after
tripping.
NOTICE
The motor may start without warning. If the specified
number of AUTOMATIC RESETs is reached within 10
minutes, the frequency converter enters Manual reset [0]
mode. After the Manual reset is performed, the setting
of
parameter H-04 Auto-Reset (Times)
reverts to the
original selection. If the number of automatic resets is
not reached within 10 minutes, or when a Manual reset
is performed, the internal AUTOMATIC RESET counter
returns to zero.
H-05 Auto-Reset (Reset Interval)
Range:
Function:
10 s
*
[0 - 600
s]
Enter the time interval from trip to start of the
automatic reset function. This parameter is
parameter H-04 Auto-Reset (Times)
is set to
[1]–[13] Automatic reset
.
H-06 Fan Operation
Option:
Function:
Select the minimum speed of the main fan.
[0]
*
Auto
Select
[0] Auto
to run the fan only when the
internal temperature of the frequency
converter is in the range 35
°
C (95
°
F) to
approximately 55
°
C (131
°
F). The fan runs at
low speed at 35
°
C (95
°
F) and at full speed
at approximately 55
°
C (131
°
F).
[1]
On 50%
[2]
On 75%
[3]
On 100%
[4]
Auto (Low
temp env.)