AP-85 Speed at Design Point [RPM]
Range:
Function:
1500
RPM
*
[par.
AP-83 -
60000
RPM]
Resolution 1 RPM.
is set to
[0] Disabled
. Enter the
motor speed in RPM at which the system
design working point is achieved. Alterna-
tively, enter the speed in Hz in
parameter AP-86 Speed at Design Point [Hz]
. If
it has been decided to use RPM in
parameter K-02 Motor Speed Unit
parameter AP-83 Speed at No-Flow [RPM]
should also be used.
AP-86 Speed at Design Point [Hz]
Range:
Function:
50.0
Hz
*
[par.
AP-84 -
par. F-03
Hz]
Resolution 0.033 Hz.
Only visible when
is set to
[0] Disabled
. Enter the
motor speed in Hz at which the system
design working point is achieved. Alterna-
tively, enter the speed in RPM in
parameter AP-85 Speed at Design Point [RPM]
.
If it has been decided to use Hz in
parameter K-02 Motor Speed Unit
parameter AP-83 Speed at No-Flow [RPM]
should also be used.
AP-87 Pressure at No-Flow Speed
Range:
Function:
0
*
[0 - par. AP-88] Enter the pressure H
MIN
corresponding to
speed at no-flow in reference/feedback
units.
AP-88 Pressure at Rated Speed
parameter AP-82 Work Point Calculation
Range:
Function:
999999.999
*
[par. AP-87 -
999999.999]
Enter the value corresponding
to the pressure at rated speed,
in reference/feedback units.
This value can be defined
using the pump datasheet.
AP-89 Flow at Design Point
parameter AP-82 Work Point Calculation
Range:
Function:
0
*
[0 - 999999.999] Enter the value corresponding to the flow
at design point. No units necessary.
AP-90 Flow at Rated Speed
Also, see
parameter AP-82 Work Point Calculation
Range:
Function:
0
*
[0 - 999999.999] Enter the value corresponding to flow at
rated speed. This value can be defined
using the pump datasheet.
Parameter Description
AF-600 FP
™
Programming Guide
DET-620D
03/2016 All rights reserved.
137