background image

·�· 

Polyphase  Switchboard  Watthour  Meters 

GEH7 64A8 

The  effect  of  light-load  adjustment  varies  inversely 

with  the  load.  For  example,  a  5  per  cent  change  at 

1/10  full-load  current  changes  the  calibration  at  full­
load  current  approximately  0.5  per  cent. 

INDUCTIVE  LOAD  (WAlTHOUR  STATORS) 

The  inductive-load  adjustment  is  made  by  turning 

the  screw located to the  left  of  the  light  load adjusting 

screw.  Turning  the  screw  counterclockwise  increases 
the  speed  of  the  meter  and  clockwise  decreases  it. 

If  the  lag  plate  is  moved,  full  and  light  load  should 

be  checked. 

Meters  furnished  for  25- and  30-cycle  service  some­

times  are  provided  with  an  adjustable  compensating 

coil.  The  purpose  of  this  coil  is  to  give  additional 
range  of  adjustment  for  calibrating  the  meter  at 
inductive  loads. 

The  two  ends  of  the  figure-eight  compensating  coil 

are extended beyond the  meter stator and  are  connect­

ed  by  an  adjustable  slider  soldered  in  position.  The 
wires  are  covered  with  insulation  tubing  and  both 

slider  and  wires  are  protected  by  an  outer  sleeving. 
These  adjustable  ends  of  the  coils  are  located  along 
the  edge  of  the  back  side  of  the  meter  frame. 

These  meters  are  adjusted  in  the  factory  so  that 

the  front  screw  adjustment  for  inductive  loads 
provides  a  range  sufficient  for  most  conditions  of 
operation. 

Should  it  be  necessary  to  change  this 

range,  its  limits  can  be  raised  or  lower�d  by  means  of 

the  adjustable  compensating  coil.  The  procedure  is 

outlined  below: 

1. 

Remove  the  outer  sleeving  and  inner  insula­

tion  tubing,  unsolder  the  sliding  connector  and  move 
it  to  the  desired  position. 

Move  the  connector  away  from  the  stator  to  in­

crease  the  speed  of  the  meter  and  toward  the  stator 
to  decrease  it. 

2. 

Resolder  the  connector  carefully  in  its  new 

position. 

Allow  the  connector  and  wires  to  cool  to  room 

temperature  before  checking  the  meter,  so  its  calibra­
tion  will  not  be  affected  by  the  increased  resistance  of 
the  coil due  to  heating. 

3.  When  the  connector  has  been  set  in  its  final 

position,  reinsulate  the  wires  with  the  proper  tubing 

and  replace  the  outer  protective  sleeving.  Care  should 
be  taken  to  locate  the  butt  joints  in  the  tubing  so  they 
are  not  opposite  each  other  or  a  section  of  bare  wire. 

Adjustments  Between  Stators 

Equalizing  the  torque  of  the  stators  may  be  accom-

plished  from  the  front  of  the  meters  and  without 

disturbing  any  of  the  parts. 

The  meter  stators  are  balanced  at  the  factory,  but 

if  \�  is  necessary  to  make  any  change  loosen  the  lock 

m

it

turn  the  adjusting  screws  an  equal  amount  in  the 

same  direction,  then  tighten  the  lock  nut.  Turning 
clockwise  decreases  and  counterclockwise  increases 
the  torque  of  the  stator. 

READING  THE  METER  REGISTER 

The  meter  register  is  of  the  dial  type  and  is  normal­

ly  furnished  with  a  register  ratio  so  that  it  reads  in 
primary  kilowatt-hours. 

On  meters  measuring  a  large  amount  of  power  and 

equipped  with  a  "primary-reading"  register  a  dial-face 
multiplier  is  printed  below  the  dials. 

For  a  "secondary-reading"  register  the  actual  read­

ing  must  be  multiplied  by  a  constant  which  is  the 
ratio  of  primary  energy  to  secondary  energy,  that  is, 
usually the  product  of  the  current  and  potential  trans­
former  ratios  of  the  instrument  transformers  used 
with  the  meter. 

Facing  the  meter,  one  revolution  of  the  extreme 

right  pointer  equals  10  kilowatt-hours;  one  revolution 
of  the  second,  100  kilowatt-hours, etc.,  except  in  the 
case  of  meters  which  have  a  dial-face  multiplier. 

One  division  of  a  circle,  it  will  be  seen,  corresponds 

to  one  tenth  of  the  total  amount  indicated  by  one 
complete  revolution  of  the  pointer. 

In deciding  upon  the  reading  of  a  pointer,  the  point­

er  before  it  (to  the  right)  must  be  consulted.  Unless 
the  pointer  has  reached  or  passed  the  "0"  or,  in  other 

words,  completed  a  revolution,  the  other  has  not  com­
pleted  the  division  on  which  it  may  appear  to  rest. 

For  this  reason  ease  and  rapidity  are  gained  by  read-

Guide 

bushing 

Jewel 

Fig. 

1. 

I  level 

Oiltight jewel screw 

Jewel 

setting 

plug 

www . ElectricalPartManuals 

. com 

www 

. ElectricalPartManuals 

. com 

Summary of Contents for DS-19

Page 1: ... 341 DSW 341 DSM 341 DS 35 DSW 351 DSM 35 DS 381 DSW 381 DSM 38 DS 39I DSW 39 DSM 39I DS 40I DSM 40 DSW 4 W 41 DSM 411 DS 43 DSW 441 DSM 44 GENERAL ELECTRIC GEH 764AB SupiJf sedes GEH 764AA w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 2: ...Mounting DS 41 DSW 41 DSM 41 Drawout Surface Mounting DS 44 DSW 44 DSM 44 Drawout Semi flush or Surface Mounting These instructions do not purport to cover all details or variations in equipment nor to provide for every possible contingency to be met in connection with installation operation or maintenance Should further information be desired or should particular problems arise which are not cove...

Page 3: ...alled by aligning it with the guides in the case and sliding into place The connecting plug is next inserted completing the electric circuits through the meter and locking the latch on the cradle The cover is drawn to the case by four thumb screws holding the connecting plug in place The DS 43 meter is the latest model drawout switchboard two stator polyphase meter It super sedes the DS 38 and DS ...

Page 4: ...nished with potential circuit indicat ing lamps and have special potential coils with an 4 auxiliary winding connected to these lamps as illust rated in Fig 14 METERS FOR USE WITH CURRENT TRANSFORMERS In order to utilize effectively the accuracy of these meters 2 5 ampere meters are used with instrument current transformers The current coils have double the normal turns of the standard 5 ampere me...

Page 5: ...o heating 3 When the connector has been set in its final position reinsulate the wires with the proper tubing and replace the outer protective sleeving Care should be taken to locate the butt joints in the tubing so they are not opposite each other or a section of bare wire Adjustments Between Stators Equalizing the torque of the stators may be accom plished from the front of the meters and withou...

Page 6: ... tight Jewel Screw are given with reference to Fig 1 a Remove the guide bushing by means of the combination jewel and pivot wrench b Invert the screw and allow the jewel setting plug to drop out If the plug does not drop out readily gently tap the head of the screw c By means of a wire loop oil applicator put two drops of G E Watthour Meter Jewel Oil in the reservoir of the jewel screw Allow a sho...

Page 7: ...d the disk need adjusting for proper clearance in the retarding magnet gap this may be accomplished by loosening the clamp ing screw of the guide bushing and moving the guide bushing and jewel screw assembly up or down as desired h The top bearing should then be reset by push ing the disk of the moving element up against the top of the retarding magnet gap a d the electrical driving stator gap and...

Page 8: ... r f 28thra ads L 5 r t l6 ru 1 f i Jal A l 3 j irdriii Zholos t 18 thrczads Dimension A for the DS 20 and DSW 20 is 7 in Dimension A for the DS 35 and DSW 35 is 7Ys in For the DSM 20 the dimension is 82 12 in For the DSM 35 the dimension is 8 18 in Fig 5 Dimensions and front view drilling plan Fig 6 Dimensions for Types DS 35 DSW 35 for Types DS 20 DSW 20 and DSM 20 and DSM 35 See notes I 2 and 3...

Page 9: ...earance holes for all stud Textolite projection whether or not studs are used at that location Drill H in clearance holes for the four mountmg studs 2 Contact device terminals K Y and Z are turnished for Types DSW 38 39 40 and 41 only For 25 cycle ratings of Types DSM 38 39 40 and 41 above 280 volts Y voltage for DSM 39 and 41 two extra termin ls K and Z are furnished 3 For Types DSM 38 and 39 the...

Page 10: ...W PANEL DRILLING FOR SEMI FLUSH MOUNTING FRONT VIEW DSM 43 ONLY 7 8 19 532 CASE VIEW SHOWING ASSEMBLY OF HARDWARE FOR SURFACE MTG ON STEEL PANELS SURFACE MTG Fig 11 Dimensions for Types DS 43 DSW 43 and DSM 43 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 11: ...SM 44 ONLY 5 1 68 j I G T I I I I 1 I I l I I I I I I I fl I I I I I I I f I I I I I I I l lJl___________ I 19 u I 5 1 32 CASE VIEW SHOWING ASSEMBLY OF HARDWARE FOR SURFACE MTG ON STEEL PANELS Fig 12 Dimensions for Types DS 44 DSW 44 and DSM 44 11 w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 12: ... ypes DS 19 D S 34 DS 38 and DS 40 b Types DS 20 DS 35 DS 39 and DS 41 Fig 14 Showing connections of open potential circuit indicating lamps to auxiliary potential windings front views Source Fuscu _Xt Potcnt el Transformer r o 1 I 1 i 4 I I Hl lr H tt t t o I I Currcr lt fl Tran formcr j 1 1 L __s _J load With Current and Potential Transformers NOTE For 3 wire 2 phase circuits wire A should be th...

Page 13: ...1 Baek view Loed Currant tref lafom lcr r I L_ _j With Current Transformers Load With Current and Potential Transformers Fig 17 Connections for Types DS 19 and DS 34 for 4 wire Y 3 phase circuits back views Source N 3 2 1 Load 1 Current Transformer 6 l I I L I 1 I I I L _ _j With Current Transformers LOed I i L _j With Current and Potential Transformers Fig 18 Connections for Types DS 20 and DS 35...

Page 14: ...ormers With Current and Potential Transformers Fig 19 Con ns for Tyf DS 40 and ns 4e ingie 2 Jbac _ k i J N 3 2 1 Fig 20 Connections for Types DS 38 DS 40 and DS 43 4 wire Y 3 ph se back view Back view Ht Load Xt p r H r Potential f transformczr Current transformer t R 9P JSC I7C f 1 I M I I I I I jc i L9P7C0 p 1 9 L _ o _ With Current and Potential Transformers Fig 21 Connections for Types DS 39 ...

Page 15: ...CONNECTIONS FOR TESTING BOTTOM I LEMI NT NOTE5 1 I CONc tNTRIC aiNOIH6 P05T5 o R EO THUMB NUT CONNECT TO 5TU05 b LACK THUMe NUTS ENGAGE METER INTERNAL CONNECTIONS 2 REMOVABLE liNKS MUST LOCAH D 5HOWN Bt F OQE IN I ITING PLIJ i Fig 22 Field testing connections for Types DS 38 DS 40 and DS 43 using test plug model 12XLA12Al tr1 t LOAD t 1 tr1 00 0 0 0 0 tr1 r 0 CD 0 t 1 n r o 0 0 0 a s 00 0 r 0 c CD...

Page 16: ...TOM ELEMENT FQONT VI CW Fig 23 Field testing connections for Types DS 39 DS 41 and DS 44 using test plug model 12XLA12Al 5 HOn 2 p CONNE CTIONS FOR TESTING THRI I r LEMfNTS WITH POTeNTIAL COILS IN MULTIPLE AND CURQENT COILS IN 5 QIES FQONTVIEW u f r j_ _ _ _ __ 1 _ __ __ j t t i 00 2l c n 0 2l 2l n 0 2l t c a 00 j w E l e c t r i c a l P a r t M a n u a l s c w E l e c t r i c a l P a r t M a n u ...

Page 17: ...T RELAYS Types IACSlA IACSlB IACSlC IACSlD IACSlR IAC52A IACS2B G E N E R A L E L E C T R I C J zm it Eriit t n a 3 a res I 7 a 9 11 X r L w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 18: ...ATIONARY CONTACT LEFT SEAL IN UNIT STATIONARY CONTACT RIGHT SEAL IN MOVING CONTACT A SS EM TAP BLOCK T IME OIAL DISK DRAG MAGNET A Front View fig I The Induction Unit for Type lAC Relays B R ear View l 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 19: ... U Ye One Fig 19 1 ig 13 No Three Fig 20 Fig 14 Ye One Fig 19 Fig 15 No No One Fig 19 Fig 16 One Fig 19 Fig 17 molded inner and outer blocks between which nests a removable connecting plug which completes the circuits The o u t e r blocks attached to the case have the studs for the external connections and the inner b 1 o c k s have the terminals for the internal cannections The relay mechanism is...

Page 20: ...r r r r r r t o r r r r i o r r 1 r 1 r 9 lO MULTIPLES OF loiiNIIoiUiol CLOSING CURRENT r 20 Fig 2 Time current Curves of Type lAC Relays ith Inverse time Lharacteristics I T lol 10 D 9 I A 8 L 6 E 5 T T 3 N 2 G l 0 5 w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 21: ... 5 and 2 0 amperes The current closing rating of the contacts is 30 amperes for voltages not exceeding 250 volts The current carrying ratings are affected by the selection of the tap on the target and seal in coil as indicated in the following table Amperes AC or DC Function 2 Amp Tap 0 2 Amp Tap Tripping Duty 30 5 Carry Continuously 4 0 8 The 2 ampere tap has a d e resistance of 0 13 ohms and a 6...

Page 22: ... P LES O F M I N I MUM TAP SETT I NG F i g 3 Satu rat i on Cu rves for Lowest Taps of the I n duct i on Un i t of Type 1AC Rei ay s wi th I nverse t i me Character i st ics 2 5 1 1 60 t U 50 TAP RANGE 0 5 2 0 25 TAP RANGE 60 1 5 6 0 50rv AMPS TAP 60 RA NGE 25 4 16 50 AMPS w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 23: ...s U sed i n Conj u nc t i on W i th T r i pp i n g Reactors for Protect i on o f a Th ree Phase C i rcu i t I HE Time Overcurrent Relays Type lAC F i g 4 E x t e rn a l Con n ec t i on s o f Th ree T y p e I ACS I A Rel ays Used For Phase to Phase and Gr ound O v e rcu rren t P ro t ec t i on of a 3 P h a s e C i rcu i t Jl t t A BUS J I 2 A C TR I PPIOG 1EE x1 IJI I j ll J 1 er _j f i g 6 E x te ...

Page 24: ...TING CHARACTERISTI CS The instantaneous element operates over a 4 to 1 range and has its calibration stamped on a scale iii OPERATING COIL IH TARGET STATIONAfiV CONTACTS MOVING CONTACT ASS MIIL Y F i g 7 Type l AC Rel ay W i th An I nstantaneous Un i t 8 mounted beside the adjustable pole piece Time current characteristics are showJl in Fig 10 RATINGS The instantaneous element is designed to use e...

Page 25: ... transformer Normally most of the flux generated by the main REA coil passes through the upper limb of the magnetic structure and holds the armature firmly against this limb When the contacts of the induction unit close the shorting coil of the REA is short circuited and cur rent flows inthis coil by transformer action causing a redistribution of flux which actuates the armature andthe REA contact...

Page 26: ... as a part of a control panel wili be shipped in cartons designed to protect them against damage Immediately upon receipt of the relay an examination should be made for any damage sustained during shipment If injury or damage resulting from rough handling is evident a claim should be filed at once with the transporta tion company and the nearest Sales Office of the General Electric Company notifie...

Page 27: ...l Connect i on s for the Type I AC5 1 R Rel ay Front V i ew Time Overcurrent Relays Type lAC 6 8 SnORT F I NC R F i g I ll I nternal Connect i ons for the Type I ACS I D Rel ay Fron t V i ew SEAL I N Uh i T F i g 1 6 I NDUCT I ON I l 3 2 SHORT F I NCEI I n ternal Connec t i on s for the Type 1 Af52A Rel ay Fron t V i ew 11 w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c...

Page 28: ...tion the relay should be inspected for tarnished contacts loose screwst or other imperfections If any t r o u b l e is founa it should be corrected in the manner described under Maintenance ADJUSTMENTS TARGET SEAL IN ELEM ENT For trip coils operating on currents ranging from 0 2 up to 2 0 amperes at the minimum control voltage set the target and seal in tap plug in the 0 2 ampere tap For trip coil...

Page 29: ... short circuit current of 3750 amperes Assume further that cur rent transformers of 60 1 ratio are used Time Overcurrent Relays Type lAC The current tap setting is found by dividing the minimum primary tripping current by the current transformer ratio In this case 450 divided by 60 equals 7 5 amps Since there is no 7 5 amp tap the 8 amp tap is used To find the proper time dial setting to give 1 9 ...

Page 30: ...MAINTENANCE The relays are adjusted at the factory and it is advisable not to disturb the adjustments If for any reason they have been disturbed the followingpoints should be observed in restoring them DIS K AND BEARINGS The lower jewel may be tested for cracks by exploringits surface with the point of a fine needle If it is necessary to replace the jewel a new pivot should be screwed into the bot...

Page 31: ... AC5lC I AC52A I AC51R I AC528 OUTl iNE r 10 32 X 3 B IITG SCREW STUD NUMBER I NG 0RONT V I EW I G 8 1 3 5 7 9 0 0 0 0 0 0 0 0 0 0 2 4 6 B 10 CASE V I EW SHOW I NG ASSEMBLY OF HARDWARE FOR SURFACE WTG ON STEEL PANELS i DR I L L 2 HOLES F i g 1 9 Out i n e and Panel Dr i l l i n l for the Type I AC5 1 A I AC5 1 B1 I AC5 1 C I AC5 1 R I AC52A and I AC52B Rel ays 15 w w w E l e c t r i c a l P a r t ...

Page 32: ...tll o Ol FOR SURFACE MTG It I 3 Q u u I0 32 ti MTG SCREW OUTLINE PANEL VIEW SHOWING ASSEMBLY OF HARDWARE FOR SURFACE MTG ON STE a PANELS PAN EL DRILLING FOR SUR F ACE MOUNTING FRONT VIEW F i g 20 Outl ine and Panel Dr i l l ing for the Type I ACS I D Rel ay G E N E R A L E L E CT R I C Hondbook Refw 7225 w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n ...

Reviews: