7
K0341 Issue No. 2
Connect the calibrator to the device to be tested:
and
Measure
mA
Press the
mode
key and select
[Measure mA]. An
external power
supply supplies a
maximum of 30 V
for the loop. The
calibrator
measures the
current of the
loop.
Closed loop
current
measurement
from transmitter
test terminal
Measure mA with
24 V*
Press
mode
key and
select [Measure mA and
24V]. The calibrator
supplies 24 V
(maximum) for the loop,
maximum 24 mA.
*
Special condition for safe use, see page 3.
Measure Volts
Press
mode
key and
select [Measure Volts],
measure range 50 V,
maximum impedance 1
Mohm.
1
+
-
Hazardous
area
Safety
barrier
Safe
area
Advanced
%
+100.0%
+20.000
mA
mA
mA ( 24V )
COM
V
*
2
Hazardous
area
+
-
Safety
barrier
Safe
area
Advanced
%
+100.0%
+20.000
mA
mA
mA ( 24V )
COM
V
3
Advanced
%
+100.0%
+24.000
mA
mA
mA ( 24V )
COM
V
21V
4
Advanced
%
+100.0%
mA
mA ( 24V )
COM
V
+50.000 V