For selectivity of fuse operation, fuse sizes should be selected as in the tables below
STS-230-25
Fuses of line A and B
(minimum value)
STS fuses
Fuses of load lines
(maximum value)
40A gG
25A gG
16A gG
25A gG
16A gG
10A gG
STS-230-40
Fuses of line A and B
(minimum value)
STS fuses
Fuses of load lines
(maximum value)
63A gG
40A gG
25A gG
40A gG
25A gG
16A gG
25A gG
16A gG
10A gG
STS-230-63
Fuses of line A and B
(minimum value)
STS fuses
Fuses of load lines
(maximum value)
100A gG
63A gG
40A gG
63A gG
40A gG
25A gG
40A gG
25A gG
16A gG
WARNING
Maximum size for fuse LB1 is 125A gG