7 SPECIFICATIONS
7
GEK-106621 7 SPECIFICATIONS
7.1 BURDENS
Burdens for the over-current units are listed in Table 7–1: BURDEN SETTINGS. Burdens decrease with in-
creasing current above minimum setting, due to the power supply shunting in the power supply circuit. Since
the power supply is the major portion of the burden, the burden for a given input current will be constant, irre-
spective of pick-up settings on both TOC and IOC units.
Figure 7–1: BURDEN CURVE
BURDENS:
0.1A / 0.5 A unit
0.45 VA
1.0A / 5.0 A unit
2.6 VA
Table 7–1: BURDEN SETTINGS
BURDEN at MINIMUM SETTING
BURDEN IN
Ω
(Z) at MULTIPLES OF
MINIMUM PICKUP
UNIT
RANGE
Hz
R
jX
Z
∠
3x
10x
20x
100x
1A
0.1 / 31.8
60
28.8
29.2
41.3
45°
9.36
2.32
1.24
0.768
5A
0.5 / 15.9
60
1.28
1.15
1.74
42°
0.394
0.094
0.052
0.034
4
55 6 7 8
1
2
3
4
55 6 7
10
2
3
4
55 6
100
3
4
1
2
33
4
10
2
33
4
100
2
0.1
2
3
4
55 6 7 8
1
2
3
4
55 6 7
10
2
5AMP Model
1AMP Model
0.1 to 3.18 A (1 Amp Relays)
Current Range: 0.5 to 15.9 A (5 Amp Relays)
Burden
in
VA