DIAC Type 66K Digital Overcurrent Relay
GE Power Management
6 ACCEPTANCE/PERIODIC TESTS
GEK-106261
6
6.9 STANDARD INSTANTANEOUS UNIT
Connect the relay as shown in Figure 6–3: DIAC TYPE 66K INSTANTANEOUS UNIT TEST SETUP. The stan-
dard instantaneous unit is designed to use one of several coils. Table 6–3: PICKUP TIMES FOR VARYING
TIME DIALS lists the pickup range, continuous current ratings and short time ratings of each of these coils.
Figure 6–3: DIAC TYPE 66K INSTANTANEOUS UNIT TEST SETUP
Table 6–3: PICKUP TIMES FOR VARYING TIME DIALS
RANGE
SUB-RANGE
SERIES OR
PARALLEL
RATINGS
CONTINUOUS
1 SECOND
0.5 to 4.0
0.5 to 2.0
SERIES
0.75
25.0
†
1.0 to 4.0
PARALLEL
1.5
50.0
†
2.0 to 16.0
2.0 to 8.0
SERIES
3.0
130.0
†
4.0 to 16.0
PARALLEL
6.0
260.0
†
10.0 to 80.0
10.0 to 40.0
SERIES
15.0
400.0
†
20.0 to 80.0
PARALLEL
25.0
600.0
†
20.0 to 160.0
20.0 to 80.0
SERIES
25.0
600.0
†
40.0 to 160.0
PARALLEL
25.0
600.0
†
†
Higher currents
I may be applied for shorter lengths of time t in accordance with the formula:
,
K = constant
SINGLE
PHASE
CURRENT
SOURCE
TIMER
T3
T1
DIAC TYPE
66K
Target
I
in
T6
T5
START
STOP
36/300 V DC
POWER
SUPPLY
CURRENT
LIMITED TO
200 mA
–
+
I
K
t
--------
=