DEH41552 INSTALLATION INSTRUCTION FOR RIGHT POLE MOUNTING ONLY
Under
v
oltage Release Device
ELECTRICAL DATA
Cat No.
(Right Pole Only)
Rated
Voltage
MA Current
Dc
Ac
TEYXU1
24V Ac
---
100
TEYXU2
48V Ac
---
50
TEYXU3
120V Ac
---
17
TEYXU4*
240V Ac
---
10
TEYXU6
24V Dc
100
---
TEYXU7
48V Dc
50
---
TEYXU8
125V Dc
18
---
TEYXU9*
250V Dc
11
---
—
Figure 1.
CAUTION:
The device is factory installed in the right
pole only. Before inspecting or beginning any maintenance
works on the breaker, it must be dis connected from all
voltage
sources, both power and control, an d breaker
placed in th e off (open ).
—
Fig ure 2.
NOTES:
1.A ny work r equiring cover removal of a sealed breaker
voids
UL
listing. The
UL
label must be destroyed.
2 .
UVR
can
n
ot be installed in bre akers code dated with
this numb er o
r
lower:
10
1
STEP
2
Removing Cover
Remove breaker c over by re moving cover screws as shown
in Figure 3. Tar must be removed and discarded to gain
access to
screw. Remove and save plastic handle and
shutter.
Push trip bar towards load end to trip mechanism.
*Rated UVR coils includes externally serious mounted
resistor.
D
ESCRIPTION
T his device is used for automatic breaker tripping when
line voltage drops below a pre-determined level.
STEP 1
Breaker
Preparation for Field Installation.
Open breaker contac
ts
by moving handle to the breaker
“OFF” position as shown in Figure 2.
—
Figure 3.
1
This accessory to be installed in Right Pole only.