background image

3

EXHAUST DIRECTION

All dryers shipped from the factory are set up for rear exhausting.
However, on electric dryers, exhausting can be to the right or
left side of the cabinet or the bottom of the dryer. On gas dryers,
exhausting can be to the right side of the cabinet or the bottom
of the dryer. Directional exhausting can be accomplished by
installing Exhaust Kit, P/N 131456800, available through your
parts distributor. Follow the instructions supplied with the kit.

EXHAUST DUCT LOCATING DIMENSIONS

GAS SUPPLY REQUIREMENTS

 Replace copper connecting pipe that is not

plastic-coated. Stainless steel or plastic-coated brass MUST

be used.

1. Installation 

MUST

 conform with local codes, or in the absence

of local codes, with the National Fuel Gas Code, ANSI Z223.1
(latest edition).

2. The gas supply line should be of 1/2 inch (1.27 cm) pipe.
3. If codes allow, flexible metal tubing may be used to connect

your dryer to the gas supply line. The tubing 

MUST

 be

constructed of stainless steel or plastic-coated brass.

4. The gas supply line 

MUST 

have an individual shutoff valve.

5. A 1/8 inch (0.32 cm) N.P.T. plugged tapping, accessible for

test gauge connection, 

MUST

 be installed immediately

upstream of the gas supply connection to the dryer.

6. The dryer 

MUST

 be disconnected from the gas supply piping

system during any pressure testing of the gas supply piping
system at test pressures in excess of 1/2 psig (3.45 kPa).

7. The dryer 

MUST

 be isolated from the gas supply piping

system during any pressure testing of the gas supply piping
system at test pressures equal to or less than 1/2 psig (3.45
kPa).

INSTALL MALE FITTINGS IN CORRECT DIRECTION

In installations where the exhaust system is not described in the
charts, the following method must be used to determine if the
exhaust system is acceptable:
1.

Connect an inclined or digital manometer between the
dryer and the point the exhaust connects to the dryer.

2.

Set the dryer timer and temperature to air fluff (cool
down) and start the dryer.

3.

Read the measurement on the manometer.

4.

The system back pressure 

MUST NOT

 be higher than

0.75 inches of water column.  If the system back
pressure is less than 0.75 inches of water column, the
system is acceptable.  If the manometer reading is
higher than 0.75 inches of water column, the system is
too restrictive and the installation is unacceptable.

Although vertical orientation of the exhaust system is
acceptable, certain extenuating circumstances could affect the
performance of the dryer:

Only the rigid metal duct work should be used.

Venting vertical through a roof may expose the exhaust
system to down drafts causing an increase in vent
restriction.

Running the exhaust system through an uninsulated area
may cause condensation and faster accumulation of lint.

Compression or crimping of the exhaust system will cause
an increase in vent restriction.

The exhaust system should be inspected and cleaned a
minimum of 

every 6 months 

with normal usage.  The more

the dryer is used, the more often you should check the
exhaust system and vent hood for proper operation.

CORRECT

INCORRECT

0

60 ft.

(18.28 m)

     48 ft.(14.63 m)

1

52 ft.

(15.84 m)

     40 ft.(12.19 m)

2

44 ft.

(13.41 m)

     32 ft.  (9.75 m)

3

32 ft.

  (9.75 m)

     24 ft.  (7.31 m)

4

28 ft.

  (8.53 m)

    16 ft.   (4.87 m)

0

30 ft.

 (9.14 m)

     18 ft. (5.49 m)

1

22 ft.

 (6.71 m)

     14 ft. (4.27 m)

2

14 ft.

 (4.27 m)

     10 ft. (3.05 m)

3

          NOT RECOMMENDED

VENT HOOD TYPE

(Preferred)

MAXIMUM LENGTH

of 4” (10.2 cm) Dia. Flexible Metal Duct

Number

 of

90°

 Turns

4”

(10.2 cm)

Louvered

VENT HOOD TYPE

(Preferred)

Number

 of

90°

 Turns

MAXIMUM LENGTH

of 4” (10.2 cm) Dia. Rigid Metal Duct

4”

(10.2 cm)

Louvered

SAME AS OTHER SIDE

(9.5 cm)

4 3/8"

(11 cm)

5 7/8"

(15 cm)

13 1/2"

(34 cm)

3 3/4"

(9.5 cm)

3 3/4"

(9.5 cm)

(6.35 cm)

2½"

(6.35 cm)

2½"

Summary of Contents for DCCH43GAWW

Page 1: ...l Requirements 2 Exhaust System Requirements 2 3 Gas Supply Requirements 3 Location of Your Dryer 4 Rough In Dimensions 5 Unpacking 5 Reversing Door Swing 5 Electrical Installation 6 Grounding Requirements 6 Electrical Connections 3 wire 7 Electrical Connections 4 wire 7 Installation 8 Replacement Parts 8 Lint Blade Retaining Pin Location 8 Printed in U S A P N 134206400 0212 Installation Instruct...

Page 2: ...ealed space of a building which can accumulate lint resulting in a fire hazard Exceeding the length of duct pipe or number of elbows allowed in the MAXIMUM LENGTH charts can cause an accumulation of lint in the exhaust system Plugging the system could create a fire hazard as well as increase drying times Do not screen the exhaust ends of the vent system nor use any screws or rivets to assemble the...

Page 3: ...st be used to determine if the exhaust system is acceptable 1 Connect an inclined or digital manometer between the dryer and the point the exhaust connects to the dryer 2 Set the dryer timer and temperature to air fluff cool down and start the dryer 3 Read the measurement on the manometer 4 The system back pressure MUST NOT be higher than 0 75 inches of water column If the system back pressure is ...

Page 4: ...SET WITH A SOLID DOOR CLOSET DOOR 1 2 54 cm 0 0 cm 4 A minimum of 120 square inches 774 2 square cm of opening equally divided at the top and bottom of the door is required Air openings are required to be unobstructed when a door is installed A louvered door with equivalent air openings for the full length of the door is acceptable MINIMUM INSTALLATION CLEARANCES Inches FRONT SIDES REAR TOP Alcove...

Page 5: ...crews 3 Rotate the door 180 and reinstall the door hinges to the dryer front panel with the four screws 4 Install the four hinge hole plugs in the open screw holes on the right side of the door opening UNPACKING 1 Using the four shipping carton corner posts two on each side carefully lay the dryer on its left side and remove foam shipping base To prevent damage do not use the control panel or coin...

Page 6: ...pper and aluminum and can cause electrical shorts The proper wiring and receptacle is a copper wired power cord with a copper wired receptacle NOTE Dryers operating on 208 volt power supply will have longer drying times than operating on 240 volt power supply For a permanently connected dryer 1 The dryer MUST be connected to a grounded metal permanent wiring system or an equipment grounding con du...

Page 7: ...NECTIONS FOR 3 WIRE SYSTEM ELECTRIC Dryer 1 Remove the screws securing the terminal block access cover and the strain relief mounting bracket located on the back of the dryer upper corner 2 Install a U L listed strain relief into the power cord entry hole of the mounting bracket Finger tighten the nut only at this time 3 Thread a U L listed 30 amp power cord NEMA 10 30 Type SRDT through the strain...

Page 8: ...es clothing etc obstructs the flow of combustion and ventilation air 6 Run the dryer through a cycle check for proper operation NOTE On gas dryers before the burner will light it is necessary for the gas line to be bled of air If the burner does not light within 45 seconds the first time the dryer is turned on the safety switch will shut the burner off If this happens turn the timer to OFF and wai...

Reviews: