APPLICATION EXAMPLE
D485 MODBUS TO DEVICENET CONVERTER – USER GUIDE
9–17
PARAMETER DATA INPUT
AREA MAPPING
The explicit data can be further assigned to different attributes of parameter data input
mapping object B0h. Define the following four attributes out of eight bytes of explicit data.
This can be done by using I/O data input area mapping mailbox command (04h)
1.
Right click on the
EndInit
item and insert a new mailbox.
2.
Set the command code to 04 (row 3).
3.
The offset and length of attribute must be provided for each of the four attributes.
Enter 16 in the Data size field - it will automatically convert and display as 0x0010.
Figure 9-28: Offset and data length for parameter data input mapping attributes
4.
The offset and data length for each attribute in bytes in given below.
5.
Enter the offset and data length values from the table above, then select the
File >
Apply Changes
menu item to save the changes.
Attribute
Bytes
Assignment
Attribute 1
2 bytes
Switch input status
Attribute 2
2 bytes
Motor load
Attribute 3
2 bytes
Thermal capacity
Attribute 4
2 bytes
Voltage
Attribute
Offset
Data length
1
0x0000
0x0002
2
0x0002
0x0002
3
0x0004
0x0002
4
0x0006
0x0002
Summary of Contents for D485
Page 32: ...3 14 D485 MODBUS TO DEVICENET CONVERTER USER GUIDE DATA EXCHANGE ...
Page 46: ...4 14 D485 MODBUS TO DEVICENET CONVERTER USER GUIDE SOFTWARE OVERVIEW ...
Page 52: ...5 6 D485 MODBUS TO DEVICENET CONVERTER USER GUIDE COMMUNICATION MODEL ...
Page 92: ...9 20 D485 MODBUS TO DEVICENET CONVERTER USER GUIDE APPLICATION EXAMPLE ...
Page 94: ...10 2 D485 MODBUS TO DEVICENET CONVERTER USER GUIDE MISCELLANEOUS ...