3–4
D485 MODBUS TO DEVICENET CONVERTER – USER GUIDE
DATA EXCHANGE
For example, when using an input I/O size of 50 and an output I/O size of 60, the input and
output data areas will be allocated as follows:
Figure 3-4: I/O data area example
Memory Map
MEMORY LOCATIONS
When configuring the sub-network, use the memory locations shown below:
•
Status register
(0x0000 to 0x0001): If enabled, this register occupies the first two
bytes in the input data area. For more information, see
•
Input data area
(0x002 to 0x01FF): This area holds data that should be sent to the
fieldbus (see the status and control registers).
•
Control register
(0x0200 to 0x0201): If enabled, these register occupies the first two
bytes in the output data area. For more information, see
•
Output data area
(0x0202 to 0x03FF): This area holds data received
from
the fieldbus.
Data cannot be written to this area.
•
General data Area
(0x0400 to 0x07FB): This data
cannot
be accessed from the
fieldbus, and should be used for transfers between nodes on the Modbus sub-
network, or as a general “scratch pad” for data.
Input data area
Output data area
50 bytes
462 bytes
(512 – 50 = 462)
60 bytes
452 bytes
(512 – 60 = 462)
I/O data (input)
I/O data (input)
Explicit data
(input)
Explicit data
(output)
Address
Contents
Access
0x0000 to 0x0001
Status register
read/write
0x0002 to 0x01FF
Input data area
read/write
0x0200 to 0x0201
Control register
read only
0x0202 to 0x03FF
Output data area
read only
0x0400 to 0x07FB
General data area
read/write
Summary of Contents for D485
Page 32: ...3 14 D485 MODBUS TO DEVICENET CONVERTER USER GUIDE DATA EXCHANGE ...
Page 46: ...4 14 D485 MODBUS TO DEVICENET CONVERTER USER GUIDE SOFTWARE OVERVIEW ...
Page 52: ...5 6 D485 MODBUS TO DEVICENET CONVERTER USER GUIDE COMMUNICATION MODEL ...
Page 92: ...9 20 D485 MODBUS TO DEVICENET CONVERTER USER GUIDE APPLICATION EXAMPLE ...
Page 94: ...10 2 D485 MODBUS TO DEVICENET CONVERTER USER GUIDE MISCELLANEOUS ...