Connections and Configuration
, continued
WESDAC
Board Jumpers
There are five jumpers on the WESDAC A, S, K and C boards, located in similar
positions on each of the boards:
Notes: The WESDAC D20A board is shown as an example.
The WESDAC D20AC board has no jumpers.
WESDAC
Jumpers Z1-Z5
Jumpers Z1 to Z5 are used to set the Base software compatibility on the WESDAC
boards.
Check what Base the D20/D200 main board is using and set the jumpers
accordingly. There are two possible settings:
•
For Base 3.11 or older
•
For any other base.
Note:
If you are replacing a WESDAC peripheral board, you will not see these
jumpers on older versions of the board.
Checking the
Base Version
Use the following table to determine which Base version you have. Inspect the
BootROM labels on D20M, D20M+ and D20M++ main boards.
BootROM labels on BASE 3.11 or older boards
D20M & D20M+ Boards
D20M++ Boards
0.41X 3.02
(SBD006/00)
1.01 3.03
(SBD007/00)
2.00 3.03A
(SBD008/00)
2.01
3.00
3.01 (SBD004/00)
3.02 (SBD003/00)
3.03 (SBD005/00)
3.03A (SBD000/00)
Jumpers Z1 to Z5
Jumpers Z1 to Z5