GE Energy
D20/D200
Installation and Operations Guide
General 994-0078-2.00-7
Full
111
D20/D200 Software Configuration
, continued
Software Configuration – D20ME II
, continued
Procedure: D20ME II - D20 Base
(continued)
Step
Action
Optional Step 2: To receive feedback during download
8
Configure the
HyperTerminal
to communicate at the same speed, and
reconnect to the 68K Monitor.
9
If the communication software you are using
does not
have a “progress
indicator’, you can enable echo to display the code file on the monitor as
it is transferred.
The echo option can be usually found in the Communication Settings or
Properties of the communication program.
Note:
Enabling echo may slow the transfer speed.
Download Code File
10
Type
dl
and press
ENTER
to ready the D20ME II to receive the
downloadable code file.
11
Click
Transfer | Send Text File
from menu bar.
Result: A dialog box opens, prompting you to locate the
Down.shx
file
that you wish to download.
12
Select the correct file, and click
Open
to start the transfer.
Result:
The file transfer may take from less than 10 minutes to
over 30 minutes, depending on the communication speed
selected.
When complete, the D20M> prompt returns.
13
Type
el /p
to display the error log.
Result: The D20M> prompt should return, indicating no errors found.
Errors? Record error(s), and re-try download.
If errors persist, contact GE for support.
14
Type
el /r
to clear the error log, even if there are no errors displayed in
the previous step.
15
Type
Boot
to restart device.
Result: The D20ME II code download is complete.