INSTRUCTIONS 

CAUTION:  Before  Installing in  a  nuclear  applica­

tion,  determine  that  the  product  Is  intended  for 

such use. 

�  DANGER 

HAZARD OF ELECTRICAL 

SHOCK OR BURN. 

COVER 

SCREWS 

JUMPER WlRE "A" 

DISCONNECT ALL POWER 

BEFORE SERVICING 
READ INSTRUCTIONS 

FOR THIS EQUIPMENT 

LOW VOLTAGE 

PROTECTION 

(LVP)UNIT 

Figure  1. CR1062RL manual motor starter with low voltage protection 

GENERAL 

The  CA1062AL 

SL  manual  motor  starters  are  designed  to 

meet  motor  starter applications  where  low  voltage protection  Is 

required.  Low  voltage protection  (LVP)  on the  CR1062RL 

SL is 

provided by a solenoid assembly which de-energizes and turns off 

the  starter  when  a  loss  of  power occurs.  The  motor  cannot  be 

restarted until power is restored and the motor starter is turned to 

the  on  position.  Terminals  are provided for the  installation of  a 

remote stop contact. The CA1062AL 

SL starters are also provid-

ed with thermal overload relays for motor overcurrent protection. 
INSTALLATION AND WIRING 

1.  Be sure line power Is off before wiring.
2. Be  sure  that  the  low voltage  protection solenoid coil is the

correct voltage. The coil voltage ls shown on the label attach­

ed to t,he LVP unit.

3.  Connect  line  and  I08.d  wires. To  Install  a  remote  stop,  see

instructions below.

4.  Select  Jhe 

proper_  ov8'rload  heaters  ·from  the  heater  table

provided with the starter and install where shown in Figure 1.

5.  Check the low voltage protection unit by"attemptlng to turn 

on the.starter with the  line power off. The starter should im­

mediately turn off when the toggle or start button is released.

The starter should remain on when the line power is on, if not,

recheck coil voltage.

INSTALLATION OF A REMOTE STOP 

1. Disconnect all power to the starter.

2. Locate: the top clamp type terminals on the LVP unit.

(Figure 1.)

3. Loosen the terminals and remove the jumper wire'' A".

(Figure 1.) 

4. Wire the remote stop pilot device  between the terminals. 

CONNECTION DIAGRAM 

� 

r,1

ra1

� 

:

e

7R:MOVE JUMP� "A"TO CONNECT 

REMOTE STOP OPERATOR. WIRE 

MOTOR 

TO VACATED TERMINALS, 
CONNECTIONS FOR 3 POLE SWITCH 

USED IN 3 PHASE, 3 WIRE CIRCUIT 

Figure 2. Typical connection diagram forCR1062RL and SL manual starters 

These instructions do not purport to cover all details or variations in equipment nor to provide for every possible contingency to be met in connection with 

installation, operation or maintenance. Should further information be desired or should particular problems arise which are not covered sufflclently for the 

Purchaser's purposes, the matter should be referfed to the nearest ABB Sales Office. 

1

GEH

-

4737 

Installation Instructions

CR1062RL and SL

manual motor starters

WITH LOW VOLTAGE PROTECTION (LVP)