background image

TRIP 

LEVER 

COILASSEM8LY 

COil LEADS 

◄ 

SCREW"8"/ 

Figure 3. Low voltage protection (LVP) unit. 

CONTACT REPLACEMENT 

1.  Disconnect  all  power  to  the  starter  and  remove  from 

enclosure.

2.  Remove LVP coil connections from starter load terminal.s.

· 3.- Remove\>tarter cover.

4. Turn starter over and remove screw "B" holding the 'L_\fp unit.

Remove LVP unit ·from starter.

5.  Locate  and  remove  the  three  screws  securing  the  upper

housing. These:are in recessed pockets In the-corners of the

upper  housing.  PUii  up  on  housing  and  remove  operating

mephanism, upp.er housing, and-tip carrier.from base.

6.  Remove overload relay heaters. 

7. Replace movable and stationary contacts. 

8. Reverse  above  procedure  to  reassemble  starter.  Be  sure

return  spring is  present.  Be  sure the tip  carrier  is properly

seated  in  the  operating  mechanism  and  that  the  starter

operates smoothly.

9. Make sure the coil leads of the LVP unit are placed In the wire 

trough (Figure 3). 

10.  Place  LVP  unit  in  original  position  and  secure  with  screw 

"B".  Before tightening starter cover screws, be sure that the 

trip  lever  (Figure  3)  is  under  the  lever  extending  from  the 

starter  body.  The  trip  lever  can  be  depressed  with  a  small 

screwdriver.  Make  sure  the  toggle  or  pushbutton  is  in  the 

original  position.  Align  LVP cover  with  slot on  starter  cover

and  tighten  starter  cover  screws.  Reconnect  coil  leads  to

starter load terminals as shown on heater table diagram.

11. Check LVP operation by attempting to turn on starter with the 

line power off. The starter should  immediately turn off when

the  toggle  or  start  button  is  released.  If  it  fails  to  turn off, 

Check to see that the  trip lever is properly  located  (see step 

10). The starter should  remain on when the line power  is on, 

if not, recheck coil voltage. 

12.  Remount starter in enclosure. 

RENEWAL PARTS 

To order Renewal Parts or to obtain information regarding parts 

not  listed, contact the nearest General Electric Sales Office. 

REPLACEMENT CONTACTS 

Device 

1 Pole 

Catalog 

Contact Kit 

Number 

CR1062R 

55-158475G001 

CR1062S 

55-1584750002 

2

 

ABB Inc. 

 

305 Gregson Drive

 

Cary, NC 27511. 

electrification.us.abb.com

  

 

We reserve the right to make technical 
changes or modify the contents of this 
document without prior notice. With 
regard to purchase orders, the agreed 
particulars shall prevail. ABB Inc. does not 
accept any responsibility whatsoever for 
potential errors or possible lack of 
information in this document. 

We reserve all rights in this document and 
in the subject matter and illustrations 
contained therein. Any reproduction or 
utilization of its contents – in whole or in 
parts – is forbidden without prior written 
consent of ABB Inc.  
Copyright© 2019 ABB  
All rights reserved 

 

GE is a trademark of GE. Manufactured 
by ABB Inc. under license from GE. 

1SQC912013M0201

 

GEH-4737

A

January 2020

Reviews: