5-178
C70 Capacitor Bank Protection and Control System
GE Multilin
5.6 GROUPED ELEMENTS
5 SETTINGS
5
5.6.6 GROUND CURRENT
a) MAIN MENU
PATH: SETTINGS
GROUPED ELEMENTS
SETTING GROUP 1(6)
GROUND CURRENT
b) GROUND TIME OVERCURRENT
(ANSI 51G, IEC PTOC)
PATH: SETTINGS
GROUPED ELEMENTS
SETTING GROUP 1(6)
GROUND CURRENT
GROUND TOC1(6)
This element can provide a desired time-delay operating characteristic versus the applied current or be used as a simple
definite time element. The ground current input value is the quantity measured by the ground input CT and is the funda-
mental phasor or RMS magnitude. Two methods of resetting operation are available: “Timed” and “Instantaneous” (see the
GROUND CURRENT
GROUND TOC1
MESSAGE
GROUND TOC2
↓
MESSAGE
GROUND TOC6
MESSAGE
GROUND IOC1
MESSAGE
GROUND IOC2
↓
MESSAGE
GROUND IOC12
GROUND TOC1
GROUND TOC1
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
GROUND TOC1 SIGNAL
SOURCE: SRC 1
Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
MESSAGE
GROUND TOC1
INPUT: Phasor
Range: Phasor, RMS
MESSAGE
GROUND TOC1
PICKUP: 1.000
pu
Range: 0.000 to 30.000 pu in steps of 0.001
MESSAGE
GROUND TOC1
CURVE: IEEE Mod Inv
Range: see the Overcurrent Curve Types table
MESSAGE
GROUND TOC1
TD MULTIPLIER: 1.00
Range: 0.00 to 600.00 in steps of 0.01
MESSAGE
GROUND TOC1
RESET: Instantaneous
Range: Instantaneous, Timed
MESSAGE
GROUND TOC1 BLOCK:
Off
Range: FlexLogic operand
MESSAGE
GROUND TOC1
TARGET: Self-reset
Range: Self-reset, Latched, Disabled
MESSAGE
GROUND TOC1
EVENTS: Disabled
Range: Disabled, Enabled
Summary of Contents for C70
Page 10: ...x C70 Capacitor Bank Protection and Control System GE Multilin TABLE OF CONTENTS ...
Page 394: ...5 270 C70 Capacitor Bank Protection and Control System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 676: ...E 10 C70 Capacitor Bank Protection and Control System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Page 698: ...H 8 C70 Capacitor Bank Protection and Control System GE Multilin H 3 WARRANTY APPENDIX H H ...