D-2
C60 Breaker Protection System
GE Multilin
D.1 IEC 60870-5-103
APPENDIX D
D
D.1.3 INTEROPERABILITY DOCUMENT
The boxes indicate the following:
– used in standard direction;
– not used.
1.
PHYSICAL LAYER
Electrical interface
EIA RS-485
32
Number of loads for one protection equipment
Optical interface
Glass fibre
Plastic fibre
F-SMA type connector
BFOC/2.5 type connector
Transmission speed
9600 bits/s
19200 bits/s
2.
LINK LAYER
There are no choices for the link layer.
3.
APPLICATION LAYER
Transmission mode for application data
Mode 1 (least significant octet first), as defined in 4.10 of IEC 60870-5-4, is used exclusively in this companion stan-
dard.
Common address of ASDU
One COMMON ADDRESS OF ASDU (identical with station address)
More than one COMMON ADDRESS OF ASDU
Selection of standard information numbers in monitor direction
System functions in monitor direction
INF Semantics
<0> End of general interrogation
<0> Time synchronization
<2> Reset FCB
<3> Reset CU
<4> Start/restart
<5> Power on
Status indications in monitor direction
INF Semantics
<16> Auto-recloser active
<17> Teleprotection active
<18> Protection active
<19> LED reset
<20> Monitor direction blocked
<21> Test mode
Summary of Contents for C60
Page 10: ...x C60 Breaker Protection System GE Multilin TABLE OF CONTENTS ...
Page 30: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 420: ...5 284 C60 Breaker Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 466: ...8 4 C60 Breaker Protection System GE Multilin 8 1 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Page 478: ...9 12 C60 Breaker Protection System GE Multilin 9 6 DISPOSAL 9 MAINTENANCE 9 ...
Page 492: ...A 14 C60 Breaker Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 648: ...E 10 C60 Breaker Protection System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Page 660: ...F 12 C60 Breaker Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 670: ...H 8 C60 Breaker Protection System GE Multilin H 2 ABBREVIATIONS APPENDIX H H Z Impedance Zone ...
Page 672: ...H 10 C60 Breaker Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...
Page 682: ...x C60 Breaker Protection System GE Multilin INDEX ...