5-148
C60 Breaker Protection System
GE Multilin
5.5 FLEXLOGIC
5 SETTINGS
5
The operands available for this relay are listed alphabetically by types in the following table.
Table 5–18: C60 FLEXLOGIC OPERANDS (Sheet 1 of 7)
OPERAND TYPE
OPERAND SYNTAX
OPERAND DESCRIPTION
CONTROL
PUSHBUTTONS
CONTROL PUSHBTN 1 ON
CONTROL PUSHBTN 2 ON
CONTROL PUSHBTN 3 ON
CONTROL PUSHBTN 4 ON
CONTROL PUSHBTN 5 ON
CONTROL PUSHBTN 6 ON
CONTROL PUSHBTN 7 ON
Control pushbutton 1 is being pressed
Control pushbutton 2 is being pressed
Control pushbutton 3 is being pressed
Control pushbutton 4 is being pressed
Control pushbutton 5 is being pressed
Control pushbutton 6 is being pressed
Control pushbutton 7 is being pressed
CYBERSENTRY
ROLE ADMIN ACT
ROLE SUPERVISOR ACT
ROLE ENGINEER ACT
ROLE OPERATOR ACT
ROLE OBSERVER ACT
AUTHENTICATION FAIL
UNAUTH FW ATTEMPT
UNAUTH SETTING WRITE
Administrator role is active and is set to true when that is the case
Supervisor role is active and is set to true when that is the case
Engineer role is active and is set to true when that is the case
Operator role is active and is set to true when that is the case
Observer role is active and is set to true when that is the case
Operand set for Failed Authentication self-test and alarm
Operand set for firmware lock self-test and alarm
Operand set for settings lock self-test and alarm
DIRECT DEVICES
DIRECT DEVICE 1On
↓
DIRECT DEVICE 16On
DIRECT DEVICE 1Off
↓
DIRECT DEVICE 16Off
Flag is set, logic=1
↓
Flag is set, logic=1
Flag is set, logic=1
↓
Flag is set, logic=1
DIRECT INPUT/
OUTPUT
CHANNEL
MONITORING
DIR IO CH1 CRC ALARM
DIR IO CH2 CRC ALARM
DIR IO CH1 UNRET ALM
DIR IO CH2 UNRET ALM
The rate of direct input messages received on channel 1 and failing the CRC
exceeded the user-specified level
The rate of direct input messages received on channel 2 and failing the CRC
exceeded the user-specified level
The rate of returned direct input/output messages on channel 1 exceeded the
user-specified level (ring configurations only)
The rate of returned direct input/output messages on channel 2 exceeded the
user-specified level (ring configurations only)
ELEMENT:
Autoreclose
(1P/3P)
AR ENABLED
AR DISABLED
AR RIP
AR 1-P RIP
AR 3-P/1 RIP
AR 3-P/2 RIP
AR 3-P/3 RIP
AR 3-P/4 RIP
AR LO
AR BKR1 BLK
AR BKR2 BLK
AR CLOSE BKR1
AR CLOSE BKR2
AR FORCE 3-P TRIP
AR SHOT CNT > 0
AR SHOT CNT = 1
AR SHOT CNT = 2
AR SHOT CNT = 3
AR SHOT CNT = 4
AR MODE = 1
AR MODE = 2
AR MODE = 3
AR MODE = 4
AR MODE SWITCH FAIL
AR ZONE 1 EXTENT
AR INCOMPLETE SEQ
AR RESET
Autoreclosure is enabled and ready to perform
Autoreclosure is disabled
Autoreclosure is in “reclose-in-progress” state
A single-pole reclosure is in progress
A three-pole reclosure is in progress, via dead time 1
A three-pole reclosure is in progress, via dead time 2
A three-pole reclosure is in progress, via dead time 3
A three-pole reclosure is in progress, via dead time 4
Autoreclosure is in lockout state
Reclosure of breaker 1 is blocked
Reclosure of breaker 2 is blocked
Reclose breaker 1 signal
Reclose breaker 2 signal
Force any trip to a three-phase trip
The first ‘CLOSE BKR X’ signal has been issued
Shot count is equal to 1
Shot count is equal to 2
Shot count is equal to 3
Shot count is equal to 4
Autoreclose mode equal to 1 (1 and 3 pole mode)
Autoreclose mode equal to 2 (1 pole mode)
Autoreclose mode equal to 3 (3 pole-A mode)
Autoreclose mode equal to 4 (3 pole-B mode)
Autoreclose mode switching is attempted, but failed
The zone 1 distance function must be set to the extended overreach value
The incomplete sequence timer timed out
Autoreclose has been reset either manually or by the reset timer
ELEMENT:
Auxiliary
overvoltage
AUX OV1 PKP
AUX OV1 DPO
AUX OV1 OP
Auxiliary overvoltage element has picked up
Auxiliary overvoltage element has dropped out
Auxiliary overvoltage element has operated
AUX OV2
Same set of operands as shown for AUX OV1
ELEMENT:
Auxiliary
undervoltage
AUX UV1 PKP
AUX UV1 DPO
AUX UV1 OP
Auxiliary undervoltage element has picked up
Auxiliary undervoltage element has dropped out
Auxiliary undervoltage element has operated
AUX UV2
Same set of operands as shown for AUX UV1
Summary of Contents for C60
Page 10: ...x C60 Breaker Protection System GE Multilin TABLE OF CONTENTS ...
Page 30: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 420: ...5 284 C60 Breaker Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 466: ...8 4 C60 Breaker Protection System GE Multilin 8 1 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Page 478: ...9 12 C60 Breaker Protection System GE Multilin 9 6 DISPOSAL 9 MAINTENANCE 9 ...
Page 492: ...A 14 C60 Breaker Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 648: ...E 10 C60 Breaker Protection System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Page 660: ...F 12 C60 Breaker Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 670: ...H 8 C60 Breaker Protection System GE Multilin H 2 ABBREVIATIONS APPENDIX H H Z Impedance Zone ...
Page 672: ...H 10 C60 Breaker Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...
Page 682: ...x C60 Breaker Protection System GE Multilin INDEX ...