CHAPTER 5: SETTINGS
TRANSDUCER INPUTS/OUTPUTS
B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
5-271
5
5.10.2 RTD inputs
SETTINGS
TRANSDUCER I/O
RTD INPUTS
RTD INPUT H1(U8)
Hardware and software is provided to receive signals from external resistance temperature detectors and convert these
signals into a digital format for use as required. These channels are intended to be connected to any of the RTD types in
common use. Specific hardware details are contained in chapter 3.
RTD input channels are arranged in a manner similar to CT and VT channels. The user configures individual channels with
the settings shown here.
The channels are arranged in sub-modules of two channels, numbered from 1 through 8 from top to bottom. On power-up,
the relay automatically generates configuration settings for every channel, based on the order code, in the same general
manner that is used for CTs and VTs. Each channel is assigned a slot letter followed by the row number, 1 through 8
inclusive, which is used as the channel number. The relay generates an actual value for each available input channel.
Settings are automatically generated for every channel available in the specific relay as shown above for the first channel
of a type 5C transducer module installed in the first available slot.
The function of the channel can be either “Enabled” or “Disabled.” If “Disabled,” there is not an actual value created for the
channel. An alphanumeric ID is assigned to the channel; this ID is included in the channel actual values. It is also used to
reference the channel as the input parameter to features designed to measure this type of parameter. Selecting the type of
RTD connected to the channel configures the channel.
Actions based on RTD overtemperature, such as trips or alarms, are done in conjunction with the FlexElements feature. In
FlexElements, the operate level is scaled to a base of 100°C. For example, a trip level of 150°C is achieved by setting the
operate level at 1.5 pu. FlexElement operands are available to FlexLogic for further interlocking or to operate an output
contact directly.
See the following table for reference temperature values for each RTD type.
RTD INPUT H1
RTD INPUT H1
FUNCTION: Disabled
Range: Disabled, Enabled
RTD INPUT H1 ID:
RTD Ip 1
Range: up to 20 alphanumeric characters
RTD INPUT H1 TYPE:
100
Ω
Platinum
Range: 100
Ω
Nickel, 10
Ω
Copper, 100
Ω
Platinum,
120
Ω
Nickel
Summary of Contents for b30
Page 10: ...x B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Page 486: ...5 278 B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Page 616: ...iv B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...
Page 632: ...xvi B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL INDEX ...