BUILD AND INSTALL THE ZONELINE
BASE PLATFORM
1.
Construct a 23
1
⁄
4
″
min. x 23
1
⁄
4
″
min. square platform
with legs to raise the platform a minimum of 8
″
.
NOTE:
The platform must have a load-bearing
capacity of 175 lbs. minimum.
1
Installation Instructions
18
WALL PLENUM AND ARCHITECTURAL LOUVER INSTALLATION
• Install the appropriate wall plenum through the exterior wall in accordance with the Installation Instructions
provided with the plenum.
IMPORTANT:
The wall plenum is not designed to carry structural loads.
Proper wall header construction is required. The plenum requires proper flashing,
shim and caulk for a weather resistant installation.
Properly square
and level plenum.
Proper header for structural
support.
Apply proper caulking
and flashing.
Architectural Louver—
RAVAL1
Exterior/Outside Wall
Case
Wall Plenum
RAVWP6 – 6
″
D x 19
3
⁄
4
″
W x 32
″
H
RAVWP8 – 8
″
D x 19
3
⁄
4
″
W x 32
″
H
RAVWP12 – 12
″
D x 19
3
⁄
4
″
W x 32
″
H
RAVWP15 – 15
″
D x 19
3
⁄
4
″
W x 32
″
H
2.
Make drain hole cutout(s):
•
Primary Drain – Centerline of drain is
approximately 5
1
⁄
4
″
from left platform edge
and 8
1
⁄
2
″
from back platform edge.
•
Secondary Drain – Centerline of drain
is approximately 6
1
⁄
2
″
from left platform edge
and 5
1
⁄
4
″
from back platform edge.
3.
Place the platform in the utility closet
with the following clearance between it
and the interior surface of the walls/door/panel:
•
4
″
min.
from front of the case –
Unit to be installed through
FRONT
of case
•
5
″
min.
from front of the case –
Unit to be installed through
SIDE
of case
•
3
″
min.
from two sides of the case
4.
Align the platform with the opening of
the wall plenum and secure to the floor
using appropriate brackets and bolts.
23
1
⁄
4
″
min.
8
″
min.
for drain
access
Cutout for drain
connection(s)
(see NOTE below)
Back of platform
Left side of platform
NOTE:
Specific cutout size
for drain connections needs
to be determined by the installer
for the given installation situation.
5
1
⁄
4
″
23
1
⁄
4
″
min.
5
1
⁄
4
″
6
1
⁄
2
″
8
1
⁄
2
″