EN

 

ATS1197

Smart card reader with keypad

Mounting the unit 

1. 

Remove power to the control panel, or 4-door DGP, as applicable. 

2. 

Remove the two front panel screws at the bottom of the RAS (see 
Figure  ), and then remove the RAS back plate. Retain the screws 
to secure the RAS later. 

3.  Position the RAS back plate (with the tamper spring at the top) 

against the mounting surface to determine the locations of 

mounting holes and for cabling access (a reduced card reading 
range may occur if mounted on a metal surface).  

4. 

Mount the back plate on a flat surface using four screws (the hole 
nearest the tamper spring must have a screw in order for the 
tamper switch to work correctly). 

5. 

Terminate the cable, as required (see wiring details below). 

6. 

For on-line mode, set the 

BUS

 address (DIP switches 1 through 4). 

For on-line mode, set the TERM switch (DIP switch 5) as required. 
For off-line mode, the TERM switch must be off (up). See DIP switch 
settings for details. 

7.  Mount the RAS on the back plate by engaging the top, and then 

lowering the RAS to be flat against the back plate. The rear tamper 
switch must be sealed for the system to work correctly. Ensure that 
the back plate tamper spring rests on the tamper switch actuator 

(protruding from the resin in the back of the RAS) when the RAS is in 
position. 

8. 

Fix the RAS to the back plate using the two screws removed earlier 

from the bottom of the RAS. 

9. 

Apply power to the control panel, or the 4-door DGP. 

10.  For online mode, use an LCD RAS on the 

BUS

 (or the system 

management software) to program polling and set up the required 
items for the new RAS. In particular, the ATS1197 RAS must be 
programmed as a non-LCD RAS. 

11.  Check that the ATS1197 is communicating correctly and verify that 

the tamper switch is working properly (i.e. "RAS Tamper" is not 
showing on the LCD RAS).  

 

 

 

 

WARNING: 

All power should be turned off to the control panel before wiring 
the RAS. 

Location of features (figure  ) 

1. Red/Green 

dual 

colour 

LED. 

2. Yellow 

LED. 

3. Red 

LED. 

4. Locking 

screws. 

Connecting control panel to keypad RAS 

Refer to the 

ATS Control Panel Installation Guide

 for instructions. 

Tamper switch 

The ATS1197 tamper switch is closed when the unit is fitted on the 
mounting plate. In operation, the LCD display will show "RAS Tamper" 
when not closed.

 

RAS DIP switch settings (figure  ) 

A row of DIP switches is located on the rear of the RAS (figure  ) and is 
used for setting the RAS address and the bus termination (TERM) 
condition. These settings are described in the following sections. 
1. 

RAS address  : 

Set the RAS address using switches 1 to 4. Switch 

in "UP" position is off, and switch in "DOWN" position is on. 

2. 

TERM switch  : 

Use switch 5 to set TERM to ‘ON’, if needed. There 

must be no more than two TERM switches or links set to ‘ON’ for 
any bus. Refer to the control panel installation guide for details 
about the use of TERM switches or links. 

 

‘ON’ is indicated as black (down). 

Example: RAS 2 = On, off, off, off.

 

Connections 

Colour Application 
Red 

+12 V nominal (8.5 to 14.0 VDC supply) 
The RAS can be powered using the bus + and – power from 

the control panel if the distance between the RAS and the 
control panel does not exceed 100 m (328 feet). Otherwise 
the RAS can be powered by AUX PWR from a DGP, or by an 
auxiliary power supply. 

Black 

0 V (DC supply ground) 

Green 

D0/D–/Clock, may be used for D0 (Wiegand data), D– 

(RS485 data), Magnetic stripe clock. Normal operating 
voltage 0 to +5 V (absolute maximum is +12 V). 

Summary of Contents for ATS1197

Page 1: ... the BUS or the system management software to program polling and set up the required items for the new RAS In particular the ATS1197 RAS must be programmed as a non LCD RAS 11 Check that the ATS1197 is communicating correctly and verify that the tamper switch is working properly i e RAS Tamper is not showing on the LCD RAS WARNING All power should be turned off to the control panel before wiring ...

Page 2: ...igned to the RAS is in alarm state Connected to a Wiegand or Magnetic Stripe interface Green Red Green On when yellow wire is at 0 V Red On when brown wire is at 0 V Yellow On when yellow AND brown wire at 0 V LED off When yellow and brown wire are between 5 14 V Yellow Not used Red Not used In offline mode the TERM switch DIP switch 5 must be off up DIP switches 1 to 4 are not used in offline mod...

Page 3: ...or Magnetic stripe See option 16 for more data on transmitted data details Menu 6 Card beep If enabled default the beeper will give a short beep when a card is badged The panel controls subsequent beeper activity Menu 7 Watchdog Offline mode only If enabled one byte of data is sent to the host every minute to indicate that the RAS is connected and operating normally If the ATS1197 tamper is active...

Page 4: ...kann 5 Schließen Sie das Kabel wie erforderlich ab siehe Verkabelungsdetails weiter unten 6 Für den Online Modus stellen Sie die BUS Adresse DIP Schalter 1 bis 4 ein Für den Online Modus stellen Sie den TERM Schalter DIP Schalter 5 nach Bedarf ein Für den Offline Modus muss der TERM Schalter ausgeschaltet sein nach oben Weitere Details finden Sie im Abschnitt mit den DIP Schaltereinstellungen 7 Be...

Page 5: ...le oder 4 Tür Controller Grün Rot Unscharf Scharf Grün wenn alle der BDT Alarmgruppe zugeordneten Bereiche unscharfgeschaltet sind oder wenn die Option Bedienteil LCD Anzeige sperrren aktiv ist Grün blinkend bei Batteriebetrieb Netzausfall oder während der Entriegelungszeit wenn der Bereich unscharfgeschaltet ist Rot wenn alle der BDT Alarmgruppe zugeordneten Bereiche scharfgeschaltet sind Rot bli...

Page 6: ...nzuzeigen oder geben Sie die Menünummer ein und drücken Sie ENTER um eine Menüoption direkt aufzurufen Menü 1 12 14 und 15 sind reservierte Menüs Menü 2 LEDs offline Wählen Sie entweder die 2 Draht Standard oder 1 Draht LED Steuerung Für die 2 Draht LED Steuerung Der braune Ader steuert die LED 1 rot scharf Ader auf Minus 0 V LED 1 rot ein Ader offen oder an 5 bis 14 V LED 1 aus Die gelbe Ader ste...

Page 7: ...S1620 1621 1622 Programmiergerät programmiert wurden Es wird das 4 Byte lange Sicherheitspasswort verwendet Datenübertragung In den folgenden Tabellen werden die Formate aufgelistet die der Kartenleser zum Übertragen von Daten verwendet Die Formate werden durch folgende Faktoren beeinflusst Online oder Offline Modus des Lesers Menü 5 Protokolloptionen Wiegand oder Magnetstreifen Menü 16 Sicherheit...

Page 8: ...Whitehorse Road Mitcham 3132 Australia EMC Technologies Pty Ltd 57 Assembly Drive Tullamarine 3043 Victoria Australia Test report reference M040929 1 IEC 60950 Test Report For ATS1197 M040929 2 Applied standards EN50130 4 1995 A1 1995 EN60950 2000 EN300330 2 v1 1 1 06 2001 Equipment class identifier RF products falling under the scope of R TTE Not Applicable X None class 1 product class 2 product ...

Reviews: