Installation and Maintenance 
Guide 

 

D

ESCRIPTION

 

 

 

For general guidelines on system planning, design, 
installation, commissioning, use and maintenance, 
refer to the EN54-14 (2001) standard and local 
regulations. 

 
DI1552

  Analogue addressable ionisation smoke detector  

DP1551

  Analogue addressable optical smoke detector 

DT1553

  Analogue addressable rate of rise heat detector  

DB304

 Detector 

mounting 

base 

S700

 Mounting 

supplement 

 
The S1500 series detectors are designed specifically for use with 
the ARITECH FP1500 series of analogue addressable fire 
detection control panels. On these systems the control panel 
communicates with the individual detectors using a unique data 
transmission protocol. The detectors continuously monitor the 
environment where they are installed and report any changes in 
smoke or heat concentration to the control panel. In turn, the 
control panel generates the alarm condition if applicable. 
The detectors have indicators that flash in a “pre-alarm” condition 
and light continuously in a ”full” alarm condition. The system is 
reset at the control panel.  
An optional remote indicator (part no. AI300) may be connected 
from the mounting base connections

 

and will mimic the detector 

indicator

  

The DP1551 and DI1552 comply with EN54-7 (2000).  

I

NSTALLATION

 

The detectors must not be exposed to dusty or dirty environments. 
During building works or repairs, the detectors must be removed. 
Smoke detectors should not be installed in environments where 
condensation may be present. 
The surface of the detector must not be painted. 

Positioning 

Smoke and temperature detectors are designed to be positioned 
on the ceiling and should be well away from ventilation inlets and 
air extractors. Once the location is decided, the detector base 
should be fitted first either to the pre-wired mounting box or direct 
to the ceiling through the S700 mounting supplement. 

Connections 

The detectors must be connected as shown in figure 

X

. The cable 

from the last detector on the loop should return to the control panel 
to close the loop. 
The positive line cable (+) must be connected to terminal 1, and 
the negative line (-) to terminal 3. If a remote indicator is used, its 
positive line cable (+) must be connected to terminal 2 in the 
mounting base and the negative to terminal 3. 
To connect the cables in the mounting base, remove a piece of 
insulation (about 1 cm in length), pass the cables through the hole 
and connect each cable in its proper location. To lock each cable, 
unscrew each mounting base connection. Slide the un-insulated tip 
of the cable under the metal piece and screw down (figure 

Y

). 

Check cable continuity before connecting. 

Addressing 

Each detector requires a numeric address between 1 and 125 for 
identification purposes. The address may be set using the PG700 
portable address programmer or the fire system control panel. 
Consult the handset or fire panel manual for more full instructions.

 

Connecting the detector to the mounting base 

Once the mounting base is in position, the detector is connected 
by inserting it and turning. To remove the detector, turn it in the 
opposite direction (figure 

[

). 

Locking catch 

All of the detector heads have a locking catch to prevent 
unauthorised removal. 
To enable locking, the locking catch must be broken (figure 

Z

). 

After connecting the detector, it will be locked in place.  
To remove a locked detector, press through the hole (figure 

\

using a screwdriver or similar, and turn. 

Testing 

 

• 

Check that all detectors are properly assembled in their 
mounting bases. 

• 

Activate the control panel and check for correct operation. 

• 

Check that all of the installed detectors are recognised by the 
control panel. If any detector is not recognised, check that no 
duplicate addresses have been assigned, check the correct 
assembly of the detector and its connection. 

• 

To test smoke detectors, apply smoke or approved aerosol 
and verify alarm condition. 

• 

To test heat detectors apply temperature using for example a 
hair dryer and verify that the detector goes into alarm. 

 
Consult the fire panel manual for further test procedures. 
 

M

AINTENANCE

 

In normal environments cleaning should be done at least every 
three or four years. It is recommended that random functional tests 
be carried out every six months. 
 

DP1551, DI1552 
 

1.  Remove the detector form the mounting base 
2.  Remove the detector cover by pressing the catch with a 

screwdriver and turning (see figure 6) 

3.  Use a vacuum cleaner or clean compressed air to remove the 

dust from the chamber. 

4.  Re-install the detector cover  
5.  Assemble again the detector in its mounting base and test it. 
 

DT1553 
 

These detectors do not require special maintenance or cleaning.  
 
Only authorised personnel must carry out adjustments. 
 

S

ECURITY CERTIFICATE 

(DI1552) 

KILSEN S.A. radioactive facilities.................................... IR-B/197/97 
The DI1552 has been approved by Spanish Industry and Energy 
Ministry, as EXEMPT from authorisation as radioactive installation. 
Approval code .................................................................. NHM-D161 
The detector corresponds exactly with approved sample. 
Quality system........................................................ ISO9001 certified 
Source manufacturer............................. Amersham International plc. 
NRPB and CIEMAT laboratories measures done, (following 
European Nuclear Energy Agency): 
 
Radioactive source..................................................... Americium 241 
Average activity ............................... 0.33 ± 0.04 µCi (12.1 ± 1.5 kBq) 
Radiation level at 0.1m...................................................... 0.01 µSv/h 
Contamination .................................................................<0.1 Bq/cm

 
Valid use period is for 10 years. It is forbidden to tamper with the 
workings of the unit or to remove any labels or signs. If radioactive 
source is suspected of being faulty, please contact KILSEN S.A. 
This certificate covers all devices with referred approval code. 