8-Area LCD RAS

Installation Instructions

2

Wiring

Figure 4

 shows the J1 and J4 (AL-1108 only) wiring terminal 

block locations.

Figure 4. Wiring terminals

J1 terminal block

Figure 5

 shows optional wiring features for the J1 terminal block 

and 

Table 1

 describes the terminals.

Figure 5. Typical J1 wiring

J4 terminal block (AL-1108 only)

Figure 6

 shows how to connect the J4 terminals to a Wiegand 

interface (not for 5V readers) and 

Table 2

 describes the termi-

nals.

Figure 6. J4 wiring

Note:  

Shielded cable must be used (Belden 8723 or equivalent).

LEDs

The unit provides status, area, and polling LEDs.

Status LEDs

The large status LEDs (

Figure 2

 on page 1) indicate:

Power.  

Green LED illuminates if AC power is available to 

the system.

Fault.  

Yellow LED illuminates for system faults or trouble.

Alarm.  

Red LED illuminates on any alarm in an area 

assigned to the keypad.

Access.  

Blue LED illuminates on both the AL-1103 and 

AL-1108 when certain system trouble conditions occur 
(missing battery). The LED also illuminates on the AL-1108 
when access is granted.

Area LEDs

The eight small red area LEDs (

Figure 2

 on page 1) illuminate 

when areas 1 to 8 or 9 to 16 are armed. The LEDs will flash on 
alarm.

Polling LEDs

The two polling LEDs (

Figure 4

) indicate:

RX.  

The RX LED flashes when polling data is being 

received on the system databus (LAN) from the control 
panel. If the LED does not flash, the control panel is not 
operational or the databus (LAN) is faulty (usually cabling).

TX.  

The TX LED flashes when the RAS is replying to 

polling from the control panel. If the RX LED flashes but 
the TX LED does not, the RAS is not programmed to be 
polled in the control panel or is addressed incorrectly.

Table 1.

J1 wiring terminals

Terminal

Description

+14V, 0V

Power supply.

D+

Data positive connection of the databus (LAN).

D-

Data negative connection to the databus (LAN).

IN

A request-to-exit (egress) button (normally open, 

momentary push-button switch), can be connected 

across the In and 0V terminals. When pressed, this 

button controls the request-to-exit function.

OUT

Open collector output, 50 mA maximum. It is the first 

output of the output control group that is assigned to 

this RAS. Refer to your Alliance system programming 

documentation for details.

ABCT 1234

Mode  Add

J4

J1

CLK DATA 0V +12V

OUT IN D- D+ 0V +14V

TX1

RX1

J4 Terminal

block

J1 Terminal

block

    DIP

Switches

Polling

LEDs

+14V

0V

D+

D-

IN

OUT

 Optional door
         control or 
auxiliary relay
         12 V relay

      50 mA max.

Optional egress
  push-button

J1

Table 2.

J4 wiring terminals

Terminal

Description

+12V, 0V

Power supply

CLK, DATA

Communication lines.

Wiegand

interface

J4

+12V

VSS(0V)

DATA

CLK

Red

Black

White

Green