5.4 International/North American Default
Parameter Settings
Setting
K-03 Regional Settings
to
[0] International
or
[1]
North America
changes the default settings for some
parameters.
lists those parameters that are
effected.
Parameter
International
default parameter
value
North American
default parameter
value
K-03 Regional
Settings
International
North America
P-07 Motor Power
[kW]
See Note 1
See Note 1
P-02 Motor Power
[HP]
See Note 2
See Note 2
F-05 Motor Rated
Voltage
230 V/400 V/575 V
208 V/460 V/575 V
F-04 Base
Frequency
50 Hz
60 Hz
F-53 Maximum
Reference
50 Hz
60 Hz
F-54 Reference
Function
Sum
External/Preset
F-17 Motor Speed
High Limit [RPM]
See Note 3 and 5
1,500 PM
1,800 RPM
F-15 Motor Speed
High Limit [Hz]
See Note 4
50 Hz
60 Hz
F-03 Max Output
Frequency 1
132 Hz
120 Hz
H-73 Warning
Speed High
1,500 RPM
1,800 RPM
E-03 Terminal 27
Digital Input
Coast inverse
External interlock
E-24 Function Relay No operation
No alarm
AN-15 Terminal 53
High Ref./Feedb.
Value
50
60
AN-50 Terminal 42
Output
No operation
Speed 4–20 mA
H-04 Auto-Reset
(Times)
Manual reset
Infinite auto reset
Table 5.1 International/North American Default Parameter Settings
Note 1: P-07 Motor Power [kW] is only visible when K-03 Regional
Settings is set to [0] International.
Note 2: P-02 Motor Power [HP], is only visible when K-03 Regional
Settings is set to [1] North America.
Note 3: This parameter is only visible when K-02 Motor Speed Unit is
set to [0] RPM.
Note 4: This parameter is only visible when K-02 Motor Speed Unit is
set to [1] Hz.
Note 5: The default value depends on the number of motor poles. For
a 4-poled motor, the international default value is 1,500 RPM, and
for a 2-poled motor, 3000 RPM. The corresponding values for North
America is 1800 and 3600 RPM, respectively.
5.4.1 Parameter Data Check
1.
Press [Quick Menu].
2.
Scroll to
Parameter Data Check
and press [OK].
Figure 5.12
3.
Select
Parameter Data Check
to view all
programming changes or
Last 10 Changes
for the
most recent.
5.5 Parameter Menu Structure
Establishing the correct programming for applications
often requires setting functions in several related
parameters. These parameter settings provide the
adjustable frequency drive with system details it needs to
operate properly. System details may include such things
as input and output signal types, programming terminals,
minimum and maximum signal ranges, custom displays,
automatic restart, and other features.
•
See the keypad display to view detailed
parameter programming and setting options.
•
Press [Info] in any menu location to view
additional details for that function.
•
Press and hold [Main Menu] to enter a parameter
number for direct access to that parameter
•
Details for common application set ups are
provided in
About Programming
AF-650 GP
TM
Design and Installation Guide
5-4
DET-767A
5
5
Summary of Contents for AF-650 GP Series
Page 3: ...Safety AF 650 GPTM Design and Installation Guide DET 767A ...
Page 9: ...Contents AF 650 GPTM Design and Installation Guide DET 767A ...
Page 19: ...Introduction AF 650 GPTM Design and Installation Guide 1 10 DET 767A 1 1 ...
Page 35: ...Installation AF 650 GPTM Design and Installation Guide 2 16 DET 767A 2 2 ...
Page 41: ...Start Up and Functional Tes AF 650 GPTM Design and Installation Guide 3 6 DET 767A 3 3 ...
Page 55: ...About Programming AF 650 GPTM Design and Installation Guide 5 10 DET 767A 5 5 ...
Page 91: ...Application Setup Examples AF 650 GPTM Design and Installation Guide 6 36 DET 767A 6 6 ...
Page 103: ...Status Messages AF 650 GPTM Design and Installation Guide 8 4 DET 767A 8 8 ...
Page 123: ...Warnings and Alarms AF 650 GPTM Design and Installation Guide 10 10 DET 767A 10 0 ...
Page 127: ...Basic Troubleshooting AF 650 GPTM Design and Installation Guide 11 4 DET 767A 11 1 ...
Page 129: ...Terminal and Applicable Wir AF 650 GPTM Design and Installation Guide 12 2 DET 767A 12 2 ...
Page 161: ...Specifications AF 650 GPTM Design and Installation Guide 13 32 DET 767A 13 3 ...