8 Specifications
8.1 General Technical Data
Mains supply (L1, L2, L3):
Supply voltage
200-240 V
±
10%, 380-480 V
±
10%, 525-600 V
±
10%, 525-690 V
±
10%
Mains voltage low / mains drop-out:
During low mains voltage or a mains drop-out, the drive continues until the intermediate circuit voltage drops below the
minimum stop level, which corresponds typically to 15% below the drive's lowest rated supply voltage. Power-up and full torque
cannot be expected at mains voltage lower than 10% below the drive's lowest rated supply voltage.
Supply frequency
50/60Hz
±
5%
Max. imbalance temporary between mains phases
3.0% of rated supply voltage
True Power Factor ()
≥
0.9 nominal at rated load
Displacement Power Factor (cos) near unity
(> 0.98)
Switching on input supply L1, L2, L3 (power-ups)
≤
7.5 kW/10 HP and below
maximum twice/min.
Switching on input supply L1, L2, L3 (power-ups)
≥
7.5 kW/10 HP and below
maximum once/min.
Switching on input supply L1, L2, L3 (power-ups)
≥
110 kW/150 HP and above
maximum once/2 min.
Environment according to EN60664-1
overvoltage category III / pollution degree 2
The unit is suitable for use on a circuit capable of delivering not more than 100.000 RMS symmetrical Amperes, 240/480/600 V
maximum.
Motor output (U, V, W):
Output voltage
0–100% of supply voltage
Output frequency
0–1000 Hz*
Switching on output
Unlimited
Accel/Decel Times
1–3600 sec.
*
Dependent on power size.
Torque characteristics:
Starting torque (Constant torque)
maximum 110% for 1 min.
*
Starting torque
maximum 135% up to 0.5 sec.
*
Overload torque (Constant torque)
maximum 110% for 1 min.
*
*Percentage relates to the adjustable frequency drive's nominal torque.
Cable lengths and cross sections:
Max. motor cable length, screened/armoured
150 m
Max. motor cable length, unscreened/unarmoured
300 m
Maximum cross section to control terminals, rigid wire
1.5 mm
2
/16 AWG (2 x 0.75 mm
2
)
Maximum cross section to control terminals, flexible cable
1 mm
2
/18 AWG
Maximum cross section to control terminals, cable with enclosed core
0.5 mm
2
/20 AWG
Minimum cross section to control terminals
0.25 mm
2
Specifications