1.1.18 Mains Supply 1 x 200 - 240 VAC
Normal overload 150% for 1 minute
Frequency converter
Typical Shaft Output [kW]
0.18
0.37
0.75
1.5
2.2
Typical Shaft Output [HP]
0.25
0.5
1
2
3
IP 20
Unit Size
M1
Unit Size
M1
Unit Size
M1
Unit Size
M2
Unit Size
M3
Output current
Continuous (1 x 200-240 V ) [A]
1.2
2.2
4.2
6.8
9.6
Intermittent (1 x 200-240 V ) [A]
1.8
3.3
6.3
10.2
14.4
Max. cable size:
(mains, motor) [mm
2
/AWG]
4/10
Max. input current
Continuous (1 x 200-240 V ) [A]
3.3
6.1
11.6
18.7
26.4
Intermittent (1 x 200-240 V ) [A]
4.5
8.3
15.6
26.4
37.0
Max. mains fuses [A]
See Section
Fuses
Environment
Estimated power loss [W], Best case/
Typical
1)
12.5/
15.5
20.0/
25.0
36.5/
44.0
61.0/
67.0
81.0/
85.1
Weight enclosure IP20 [kg]
1.1
1.1
1.1
1.6
3.0
Efficiency [%], Best case/Typical
1)
95.6/
94.5
96.5/
95.6
96.6/
96.0
97.0/
96.7
96.9/
97.1
Table 1.6: Mains supply 1 x 200 - 240 VAC
1.
At rated load conditions.
1.1.19 Mains Supply 3 x 200 - 240 VAC
Normal overload 150% for 1 minute
Frequency converter
Typical Shaft Output [kW]
0.25
0.37
0.75
1.5
2.2
3.7
Typical Shaft Output [HP]
0.33
0.5
1
2
3
5
IP 20
Unit Size
M1
Unit Size
M1
Unit Size
M1
Unit Size
M2
Unit Size
M3
Unit Size
M3
Output current
Continuous (3 x 200-240 V ) [A]
1.5
2.2
4.2
6.8
9.6
15.2
Intermittent (3 x 200-240 V ) [A]
2.3
3.3
6.3
10.2
14.4
22.8
Max. cable size:
(mains, motor) [mm
2
/AWG]
4/10
Max. input current
Continuous (3 x 200-240 V ) [A]
2.4
3.5
6.7
10.9
15.4
24.3
Intermittent (3 x 200-240 V ) [A]
3.2
4.6
8.3
14.4
23.4
35.3
Max.mains fuses [A]
See Section
Fuses
Environment
Estimated power loss [W], Best case/
Typical
1)
14.0/
20.0
19.0/
24.0
31.5/
39.5
51.0/
57.0
72.0/
77.1
115.0/
122.8
Weight enclosure IP20 [kg]
1.1
1.1
1.1
1.6
3.0
3.0
Efficiency [%], Best case/Typical
1)
96.4/
94.9
96.7/
95.8
97.1/
96.3
97.4/
97.2
97.2/
97.4
97.3/
97.4
Table 1.7: Mains supply 3 x 200 - 240 VAC