background image

PROBLEM

AIR CONDITIONER
DOES 

 OPERATE

AIR CONDITIONER

“DOES NOT COOL

AS IT SHOULD”

OPERATING
SOUNDS

WATER DRIPPING
OUTSIDE

WATER DRIPPING
INSIDE

WATER IN BASE PAN

(ON OUTDOOR SIDE)

POSSIBLE CAUSE AND REMEDY

● 

Not plugged in. Plug may have been bumped loose by vacuum cleaner or furniture.

. If plugged in, fuse could have blown or circuit breaker may have tripped.

. Curtains, blinds or furniture blocking front of air conditioner will restrict airflow.

● 

Thermostat Control may not be set high enough. Turn control to a higher number.

Highest setting should provide maximum cooling. When Energy Saver Switch (on some
models) is set at SAVE, temperature range in room will vary more.

● 

Air filter dirty, should be cleaned at least every 30 days. See instructions on page 5.

● 

Room may have been very hot when air conditioner was first turned on. Allow time for

it to cool down.

● 

Cold air maybe escaping through open furnace floor registers and cold air returns.

● 

Ventilation control maybe set at open position, allowing hot outside air to enter

the room.

● 

Cooling coils have iced up. To melt ice, set the Selector Switch to HIGH FAN and the

Thermostat Control to a lower number.

● 

Thermostat click, a metallic sound, maybe heard when compressor cycles on and off.

This is normal.

● 

Fan runs continuously when Selector Switch is in Cool or Fan position. This is normal.

When Energy Saver Switch (on some models) is set at SAVE, fan cycles on and off with
compressor.

● 

Excess water may overflow in extremely hot and humid weather. This is normal.

● 

Air conditioner must be installed with the specified tilt to the outside for proper water

disposal.

● 

This is normal for a short period in areas with little humidity; normal for a longer

period in very humid areas. Moisture removed from indoor air drains to rear of cabinet
where it is picked up by a fan ring and thrown against the outdoor condenser coil.

If 

 need more help.. call, toll free:

GE Answer Center

o-

800.6262000
consumer information service

If You Need Service

To obtain service, see your warranty
on the back page of this book.

We’re proud of our service and
want you to be pleased. If for some

reason you are not happy with the
service you receive, here are three
steps to follow for further help.

FIRST, contact the people who
serviced your appliance. Explain

why you are not pleased. In most

FINALLY, if your problem is still

cases, this will solve the problem.

not resolved, write:

NEXT, if you are still not pleased,

Major Appliance

write all the details-including

Consumer Action Panel

 

 number—to:

20 North 

 Drive

Manager, Consumer Relations
GE Appliances
Appliance Park
Louisville, Kentucky 40225

Chicago, Illinois 60606

6

Summary of Contents for AED18 Series

Page 1: ...m Solver 6 arc and leanin 5 Repair Service 6 ondenser oils 5 Safety Instructions 2 ontrol Settings 3 4 User Maintenance Instructions 5 Electrical Requirements 7 Warranty Back lover Elnergy Saver Switch 3 F nergy Saving Tips 2 F xtension ords 7 lrille and abinet 5 GEAnswer Centera rounding 7 800 626 2000 Models AES15 AED18 AES18 AES23 GEApp ances ...

Page 2: ...illed in accordance with the Insbllation Instructions before it is used See grounding instructions on page 7 Never unplug your air conditioner by pulling on the power cord Always grip plug firdy and pull straight out from the receptacle Repair or replace immediately all electric service cords that have become frayed or otherwise damaged Do not use a cord that shows cracks or abrasion damage along ...

Page 3: ... so equipped NORMALm ENERGY SAVER SAVE The Energy Saver Switch controls the fan operation When it s in OPEN DCLOSEO VENTIMTION Ventilation Control The vent door in your air conditioner is closed when the slide switch is to the right When the vent is closed onl the air inside the room can be circulated and conditioned Sliding the knob to the left opens the vent door allowing a small amount of indoo...

Page 4: ... Set the Ventilation Control at CLOSED 4 Set the Energy Saver Switch at the NORMAL position Note When the Energy Saver Switch is at the SAVE position changes in the sound level may be more noticeable than when it s at the NORMAL position For nighttime operation During the cooler evening hours we recommend that you set the Selector Switch at LOW COOL for very quiet operation and the Thermostat Cont...

Page 5: ... the lower part of the inlet baffle toward you and pull the filter down and out Vacuum the filter on the dusty side to remove light dust Wash the filter cleaner side up under gently flowing water to wash out accumulated dust and lint If the filter is very dirty use a mild household detergent in the wash water Let the filter dry thoroughly before replacing it Front Grille Removal The front grille c...

Page 6: ...and off This is normal Fan runs continuously when Selector Switch is in Cool or Fan position This is normal When Energy Saver Switch on some models is set at SAVE fan cycles on and off with compressor Excess water may overflow in extremely hot and humid weather This is normal Air conditioner must be installed with the specified tilt to the outside for proper water disposal This is normal for a sho...

Page 7: ...eating wires Q 230 208 VOLT MATCHING PERPENDICULAR TYPE WALL OUTLET LINE CORO PLUG REQUIRES 20 AMP TIME DELAY FUSE OR CIRCUIT BREAKER PROTEUION 230 208 VOLT MATCHING TANDEM TYPE WALL OUTLET LINE CORD PLUG REQUIRES 15 AMP TIME DELAY FUSE OR CIRCUIT BREAKER PROTECTION o 0 mm 230 208 VOLT MATCHING LARGE TANOEM TYPE WALL OUTLET LINE CORO PLUG REQUIRES 30 AMP TIME DELAY FUSE OR CIRCUIT BREAKER PROTE lO...

Page 8: ... blade type screwdriver Adjustable wrench or pliers Rule or tape measure Pencil Sharp kife or razor blade For thru the wall installation All the tools above except bife or razor blade plus Hand saw Hammer Level Chisel Caulting gun Concrete saw if installing through a masonry wall Window Requirement Standard double hung window with actual opening width of 32 to 38 Clear vertical opening of 201 2 No...

Page 9: ...oam pads inside the cabinet Note Handle is N intended for lifting the unit It is only for sliding the chassis out of the cabinet for cleaning or maintenance 2 Instill Top Angle and Side Retainers 1 Attach foam gasket o to top angle as shown 4 x I 1 2 Install top rail and side retainers to cabinet as shown using 10 Type F screws E Window Filler Panel 1 m Top View r 3 Assemble Window Hller Wneh 1 Pl...

Page 10: ...red later 1 I 3 Install support brackets with sill angle brackets attached to cabinet as shown 4 Tighten all 6 bolts securely 6 Etiend Window Hller Panek 1 Carefully raise window to expose filler panel locking screws Loosen screws so panels slide easily 2 Extend panels to fill window opening completely and tighten locking screws on top 3 Close window behind top rail 10 7 Install Window hck and Sas...

Page 11: ...ch dimension use shims to eliminate distortion t 18 5 8 8 I 4 Caulk all four sides on the outdoor side of cabinet to revent moisture from getting thr ugh to the interior wall Use of flashing a piece of aluminum or galvanized steel available at most hardware Holes for 10 1 Long c Wood Screws 0 Cabinet Be sure handle at bottom of unit is up Then lift chassis and carefully slide it into cabinet Do no...

Page 12: ...CARE SERVICE WHAT IS N COVERED Service trips to teach you how to use the product Read your Use and Care material If you then have any questions about operating the product please contact your dealer or our Consumer Affairs office at the address below or call toll free GE Answer Cente 800 626 2000 consumer information service Improper installation If you have an installation problem or if the air c...

Reviews: