background image

DEH40157 

DEH40157   Rev.No.01 

6

 

 

Figure 5. Distance between Crossbar and TEY breaker 

 
 
 
 
 
 

These instructions do not cover all details or variations in equipment nor do they provide 
for every possible contingency that may be met in connection with installation, operation, 
or maintenance. Should further information be desired or should particular problems arise 
that are not covered sufficiently for the purchaser’s purposes, the matter should be 
referred to the GE Company. 
 
 
 
 
 

 

Summary of Contents for A II Series

Page 1: ...e to install a TEY circuit breaker kit Call out numbers in the illustrations and numbers in brackets in the text refer to the Item Numbers in Table 1 Installation of a three pole kit is illustrated in Figure 1 1 Remove the interior assembly from its packaging and verify that all parts are present as given in the parts list 2 Remove the 8 screws 600A and 800A panels securing the dead front to panel...

Page 2: ...e breaker as shown in fig 1 such that breaker strap hole aligns with breaker mounting strap tapped hole and other end of breaker snaps with 3X base lancing slot provided and then tighten terminal screws completely with 27 36 in lb 6 Remove the eight screws 6 of existing one filler plates from dead front where the TEY breaker needs to be installed as illustrated in Figure 2 ...

Page 3: ... filler plate 5 over the dead front so that the four same size holes line up with the threaded holes of the dead front as illustrated in Figure 3 Fasten filler plate to the dead front with four 10 32 x 3 8 screws 6 tightened to 27 36 in lb 8 Reattach the dead front to the interior with the 8 screws removed in step 2 Tighten the screws to 27 36 in lb ...

Page 4: ...SG or SF TFJ or SE TED TQD as shown in Figure 4 then gap between the breakers dim A has to be followed as mentioned in Table 2 Replace the subsequent blank filler of dead front with TEY filler plate given in kit ASPP6EY6D using steps 9 to 11 13 If TEY breaker has to installed immediate after crossbar as shown in Figure 5 then gap between the breaker and crossbar has to be 0 06inch ...

Page 5: ...DEH40157 DEH40157 Rev No 01 5 Figure 4 Distance between breakers Table 2 Distance between breakers Breaker A in SG 0 582 SF TFJ 1 875 SE TED 6P 1 875 FB TQD 6P 1 875 ...

Page 6: ...ariations in equipment nor do they provide for every possible contingency that may be met in connection with installation operation or maintenance Should further information be desired or should particular problems arise that are not covered sufficiently for the purchaser s purposes the matter should be referred to the GE Company ...

Reviews: