background image

OPM_NPE_19X_600_1K5_2GB_V030

2

GE DE NetPro 19” 600-1500: User manual 3.0 (GB)

g

GE Digital Energy 

1.1

Introduction

The 

General Electric (GE) Digital Energy NetPro 19” UPS

, a truly on-line uninterruptible power supply,

protects your equipment from all forms of power interference, including complete power failures.

1.2

Safety Rules

x

CAUTION:

 RISK OF ELECTRICAL SHOCK

. The UPS contains batteries. The appliance

outlets may be electrically live, even when the UPS is disconnected from the mains.

x

The UPS contains potentially hazardous voltages. Do not open the UPS, there are no user

serviceable parts inside.

x

All maintenance and service work, 

except for replacement of the batteries

, should be

performed by qualified service personnel.

1.3

Transport / Storage

x

No liability can be accepted for any transport damage when the equipment is shipped in non-

original packaging.

x

During transport the battery drawer must either be removed or fixed with two screws at the rear

side of the UPS (A, fig. 1).

x

Store the UPS in a dry location with the batteries in a fully charged state. Storage temperature

must be within -20 +45 

q

C. If the unit is stored for a period exceeding 3 months, optimal battery

lifetime is obtained if the storage temperature does not exceed 25°C.

x

If the unit is stored for an extended period of time, the batteries must be recharged periodically.

Be sure that the battery drawer is connected to the UPS. Subsequently connect the unit to a wall

outlet and recharge the batteries for 24 hours:

- if the storage temperature is within -20 and +30°C: every 3 months,

- if the storage temperature is within -20 and +45°C: every month.

Please note that with completely discharged batteries the UPS will not start at all. External

charging or replacement of the batteries will be necessary.

The shipping box contains a 

NetPro 19”

 UPS, two IEC male-female power cords, a data cable, a CD

ROM

 

and this manual. Inspect the UPS for damage after unpacking. If any damage is present please

immediately notify the carrier and place of purchase.

IMPORTANT

:

Before making any connection and switching on the 

NetPro 19”

 UPS, please check the following

conditions:

x

your mains supply is 220 - 240 Volts and 50 Hz (if the mains frequency is 60Hz, the output

frequency of the UPS can be changed, see section 3.4), and

x

the total power demand of the connected equipment does not exceed the rated output power of

the 

NetPro 19”

 UPS (indicated on the rating label).

WARNING

Connecting the UPS output to neutral or ground will result in a malfunctioning UPS.

2.1

Installation Rules

x

The UPS is intended to be used in normal domestic and office situations.

x

Protect the UPS, according to the wiring rules, with a 16A D-type fuse.

x

The UPS must be powered from a single phase grounded wall outlet. Do not use extension

cords.

x

Avoid locations that are excessively humid, near water, near heat sources or in direct sunlight.

x

The ambient temperature should not exceed 40

q

C. Optimal battery lifetime is obtained if the

ambient temperature does not exceed 30

q

C.

x

It is important that ventilation air can move freely around and through the unit. Do not block the air

vents.

x

Do not plug appliances such as electric heaters, toasters and vacuum cleaners into the UPS.

x

Be careful when connecting laser printers: be sure that the demanded power does not exceed the

capacity of the UPS.

x

The sum of the leakage currents of the UPS and the connected loads should not exceed 3.5mA.

1  -  Introduction

2  -  Installation

Summary of Contents for 600 - 1500 VA

Page 1: ...anufactured by GE Digital Energy General Electric Company Telephone 41 0 91 850 51 51 CH 6595 Riazzino Locarno Fax 41 0 91 850 51 44 Switzerland Website www gedigitalenergy com GE Digital Energy Technology for the Digital World ver 3 0 GB NetPro 19 UPS g ...

Page 2: ...tions 3 2 2 Load indication 3 2 3 Auto off no load shutdown 3 2 4 Automatic bypass switch 3 2 5 Switching off 3 3 Use Status and Alarm Indications 3 3 1 Charger on 3 3 2 On line normal operation 3 3 3 On battery 3 3 4 Battery low end of runtime 3 3 5 On bypass 3 3 6 Bypass out of limits 3 3 7 Overload 3 3 8 Overtemperature 3 3 9 Replace battery 3 3 10 Programmed shutdown 3 4 Use Setup Mode 3 5 Bat...

Page 3: ...se note that with completely discharged batteries the UPS will not start at all External charging or replacement of the batteries will be necessary The shipping box contains a NetPro 19 UPS two IEC male female power cords a data cable a CD ROM and this manual Inspect the UPS for damage after unpacking If any damage is present please immediately notify the carrier and place of purchase IMPORTANT Be...

Page 4: ...4 Switch off your computer and unplug it from the socket outlet 5 Disconnect the power cord from the computer rating 250Vac 10A and connect this cord to the mains input socket 5 fig 1 of the UPS See fig 4 6 Using the output cord s provided connect the computer s to the appliance outlet s 1 fig 1 of the UPS Spread the loads over the appliance outlets as equally as possible If you use a distribution...

Page 5: ...h off during a mains failure when the load is less than 5 of the maximum load In this way unnecessary discharging of the batteries is avoided The unit will automatically turn on again when mains power is restored The default setting of the no load shutdown function is activated Changing of the setting is described in 3 4 3 2 4 Automatic bypass switch The UPS is equipped with an automatic bypass sw...

Page 6: ...ld be taken Indicators on front panel Situation on alarm on by pass progr shutd repl batt on batt buzzer o Charger on 3 3 1 o Normal operation 3 3 2 On battery 3 3 3 1x 8 s Battery low 3 3 4 1x s On bypass 3 3 5 1x s Bypass out of limits 3 3 6 1x 8s Overload 3 3 7 1x s High temperature 3 3 8 1x s Replace battery 3 3 9 o Progr shutdown pending 3 3 10 1x 8s o Progr shutdown in progress 3 3 10 Operat...

Page 7: ... also 3 2 2 If 4 yellow LEDs and the red LED illuminate bypass operation is caused by an overload If only yellow LEDs illuminate the red LED is off during load indication bypass operation is caused by overtemperature Take appropriate measures reduce load and or temperature 3 3 6 Bypass out of limits The mains voltage or mains frequency are outside bypass input tolerance but inside UPS input tolera...

Page 8: ... failure occurs during the sleep period and the battery capacity eventually drops below 80 of the normal capacity the UPS will automatically switch off in order to save battery power When the mains returns the UPS will start up automatically The programmed sleep time however is lost The programmed shutdown in progress can be cancelled x press keypad I for at least 5 seconds to cancel shutdown and ...

Page 9: ...battery test to be initiated through the UPS software via the RS232 port checks the actual battery capacity in order to ensure accurate runtime prediction During a deep battery test the batteries will be discharged until battery low alarm level Please note that immediately after a deep battery test the expected runtime is very short allow the UPS to recharge its batteries For details please refer ...

Page 10: ...s no longer guaranteed due to other circumstances than already indicated by pin 6 7 9 Output converter overload Overtemperature pre alarm High charger voltage Bypass out of limits Inverter shutdown due to inverter failure or batt failure 4 2 Relay Interface Card option The card is equipped with potential free change over contacts for the following alarms mains failure general alarm battery low byp...

Page 11: ... free take care of proper environmental conditions and keep air inlets outlets free of dust Please read 2 1 6 2 Batteries 6 2 1 General The service life of the battery is from 3 to 6 years depending on the operating temperature and on the number of discharge cycles As a healthy battery is critical to the performance of the UPS an automatic quick battery test is performed regularly to ensure failsa...

Page 12: ...ttery compartment Use a screw driver or pen as a lever 3 Remove the two screws that hold the battery drawer 4 Disconnect the DC connectors Use a screwdriver as a lever 5 Remove battery drawer Be careful heavy weight 6 Remove clamp two screws and replace the batteries 7 Reinstall battery clamp do not pinch or clamp the wires 8 Slide in the battery drawer 9 Connect the DC connectors a small spark is...

Page 13: ...Line cord not connected Read 2 2 Connect line cord Dead wall socket outlet or mains voltage out of limits Contact qualified electrician UPS overtemperature See 3 3 8 Allow UPS to cool down UPS will not switch on without using battery start and the output has been off for a few secs see also 3 2 5 Tripped Thermal Circuit Breaker See above UPS will not switch on after installation LED on remains off...

Page 14: ...ut voltage range 195 264 V Frequency tracking rate 2 Hz sec Frequency tracking range nominal 10 Phase difference 7º Typical transfer time msec 4 Overload capability Fully protected against overload and short circuits Overload behaviour battery operation 110 during 5 minutes 150 during 5 seconds Overload behaviour during depends on rating of thermal circuit breaker bypass operation typical 125 of T...

Reviews: