OPM_NPE_19X_600_1K5_2GB_V030
12
GE DE NetPro 19” 600-1500: User manual 3.0 (GB)
g
GE Digital Energy
Whenever a malfunction occurs, first check external factors (e.g connections, temperature, humidity or
load) to determine whether the problem is caused by the unit itself or by its environment. Subsequently
check the thermal circuit breaker: it may be tripped. If so: reset it (see 4, fig.1) and be sure that the UPS is
not overloaded.
The following chart is a simple troubleshooting checklist only. If the suggested solution does not succeed,
or if the information is insufficient to solve the problem, please contact your dealer or consult
www.gedigitalenergy.com.
PROBLEM
POSSIBLE CAUSE
SOLUTION
UPS overload
Reduce load, reset TCB
(4, fig. 1)
Thermal Circuit Breaker (TCB)
tripped
System failure
Contact your dealer or consult
www. gedigitalenergy.com.
Most probably an overload
See 3.3.7, reduce the load
LED 'on bypass' blinks
Overtemperature
See 3.3.8
Allow the UPS to cool down
Line cord not connected
Read 2.2
Connect line cord
Dead wall socket outlet, or
mains voltage out of limits
Contact qualified electrician
UPS overtemperature
See 3.3.8
Allow UPS to cool down
UPS will not switch on (without
using 'battery start')
and the output has been off for
a few secs. (see also 3.2.5)
Tripped Thermal Circuit Breaker
See above
UPS will not switch on after
installation, LED 'on' remains off
Batteries have been discharged
too deep during transport and/or
storage
Contact your dealer or consult
www. gedigitalenergy.com
UPS overtemperature
See 3.3.8
Allow UPS to cool down
Mains failure, battery
discharged
Wait until mains returns
Programmed shutdown in
progress
See 3.3.10
UPS received shut down
command from computer during
mains failure
Wait until mains returns
UPS switched off automatically
The load is < 5% of the max.
load and no mains power is
present.
(No-load shutdown function is
active, see 3.2.3)
Wait until mains returns
Battery test just after installation
or mains failure
Allow the UPS to recharge the
batteries
LED ‘replace battery’
illuminates, buzzer is silent
Battery test shows weak battery
Read 6.2, replace batteries
7 - Troubleshooting