background image

2

ESL 429/449

Installation

The detectors mount to standard single-gang electrical boxes,
four-inch octagonal or four-inch square electrical boxes, or on
WIREMOLD No. 5739 fixture boxes. The detectors may also be
mounted directly to walls or ceilings where local codes/
jurisdictions permit.

1. Pull wire through the electrical box and connect to the plug-in

terminal block supplied, one wire per terminal. See Figures 3
and 5.

2. Dress wiring neatly and snap the terminal block into the back

of the detector.

Note

The detector cover must be closed completely, to sup-
port the circuit board, while installing the terminal
block.

3. Open the cover and mount the detector, using the mounting

holes provided. See Figure 4.

Note

Positive air pressure from wire openings, conduit,
mounting boxes, irregular mounting surfaces, or
plenums causing air movement through and away from
the detector may prevent proper operation. Seal all
openings causing unwanted air flow using UL Listed
expanding foam or Duxseal.

4. Remove the red plastic dust cover from the detector. The

detectors are shipped with a dust cover for protection on
construction sites with dusty environments.

Figure 3. Plug-in Terminal Block

Figure 4. Detector Mounting

test switch

4” square or
WIREMOLD mounting
(No. 5739)

mounting
all boxes

single gang
4” octagon
mounting

cover release

Are More Smoke Alarms Desirable?
The required number of smoke alarms might not provide reliable
early warning protection for those areas separated by a door
from the areas protected by the required smoke alarms. For this
reason, it is recommended that the householder consider the use
of additional smoke alarms for those areas for increased
protection. The additional areas include the basement, bed-
rooms, dining room, furnace room, utility room, and hallways
not protected by the required smoke alarms. The installation of
smoke alarms in kitchens, attics (finished or unfinished), or
garages is not normally recommended, as these locations
occasionally experience conditions that can result in improper
operation.

Important !

Regulations pertaining to smoke detector
installations vary from state to state. For more
information, contact your local fire department
or local authority having jurisdiction.

In addition to NFPA 72, use the following location guidelines to
optimize performance and reduce the chance of false alarms:

•   Locate ceiling-mounted smoke detectors in the center of a

room or hallway at least 4 inches (10cm) from any walls or
partitions.

Locate wall-mounted smoke detectors so the top of the alarm
is 4 to 12 inches (10 to 30cm) below the ceiling. See Figure 2.

When more than one detector is required, spacing of 30 feet
(9m) may be used as a guide on smooth ceilings. Other
spacing may be used depending on ceiling height, high air
movement, and other conditions or response requirements.

Locate in a suitable environment as follows:

- Temperature between 32°F (0°C) and 100°F (38°C)

- Humidity between 0 and 95% non-condensing

Locate away from air conditioners, heating registers and any
other ventilation source that may interfere with smoke
entering the detector.

Locate away from kitchens, wood stoves, garages, furnaces,
and bathrooms.

Mount smoke detectors on a firm permanent surface,
typically a stud or metal runner.

Note

For instructions on removal of terminal block and
circuit board, call technical services at 800-648-7424.

Figure 2. Detector Placement

ceiling

acceptable here

never here

top of detector
acceptable here

side wall

    4”
(10cm)

    4”
(10cm)

    12”
(30cm)
maximum

Note
Measurements shown are to the
closest edge of the detector.

Summary of Contents for 429CT

Page 1: ...mily living unit occurs at night when everyone is asleep The principal threat to persons in sleeping areas comes from fires in the remainder of the unit Therefore a smoke alarm s is best located between the bedroom areas and the rest of the unit In units with only one bedroom area on one floor the smoke alarm s should be located as shown in Figure 1A In family living units with more than one bedro...

Page 2: ...tion The additional areas include the basement bed rooms dining room furnace room utility room and hallways not protected by the required smoke alarms The installation of smoke alarms in kitchens attics finished or unfinished or garages is not normally recommended as these locations occasionally experience conditions that can result in improper operation Important Regulations pertaining to smoke d...

Page 3: ...old a smoldering punk or cotton wick close to the unit and gently direct the smoke into the smoke entry openings for 20 seconds or until an alarm is indicated Be sure to properly extinguish the smoke source after testing This is a go no go test and is not a reliable indication of detector sensitivity If it is successful the LED will remain lit To reset the detector operate the system reset switch ...

Page 4: ...ical block chamber part 211 back in place Note Be sure the new optical block chamber is seated all the way down 3 Close the detector cover and verify sensitivity See Sensitivity Test Approvals The smoke detectors are for use in commercial fire protective signaling systems and in household fire warning systems NFPA 72 429 449 Series Listed by Underwriter s Laboratories California State Fire Marshal...

Page 5: ...ges prepaid to Customer Service RMA GE Security 12345 SW Leveton Drive Tualatin OR 97062 9938 A note should be included advising the nature of the malfunction Care must be exercised in the proper packing of detectors returned under this warranty as GE Security will not be responsible for warranty repairs to equipment damaged because of improper packing The above warranty is in lieu of all other ex...

Page 6: ...ate of rise 15 F min 105 F 8 C min 41 C Auxiliary relay contacts 2A 28VDC or 120VAC resistive Alarm contacts 500mA 36VDC resistive Dimensions 6 1 15 5cm diameter x 1 9 4 7cm deep Weight 8 8 oz 0 25kg Color white Wire Type Model Designator Power Designator Number Description Designator Listing Designator Power 2 Two wire only 9 UL A 6 12 VDC 4 Four wire only C 12 24 VDC Product Selection Guide 449C...

Reviews: