5–62
369 MOTOR MANAGEMENT RELAY – QUICKSTART GUIDE
SPECIFICATIONS CHAPTER 5: PRODUCT DESCRIPTION
BSD INPUTS (OPTION B)
Frequency: ........................................................1 to 120 Hz
Dynamic BSD range: ....................................20 mV to 480 V RMS
Accuracy:
...............................................±
0.02 Hz
Burden:................................................................>200 k
Ω
RTD INPUTS (OPTION R)
Wire Type: ..........................................................3 wire
Sensor Type:......................................................100
Ω
platinum (DIN 43760), 100
Ω
nickel, 120
Ω
nickel,
10
Ω
copper
RTD sensing current: ....................................3 mA
Range:..................................................................–40 to 200
°
C or –40 to 392
°
F
Accuracy:
...............................................±
2
°
C or
±
4
°
F
Lead resistance:..............................................25
Ω
max. per lead for Pt and Ni type;
3
Ω
max. per lead for Cu type
Isolation: .............................................................36 Vpk
5.2.2
Outputs
ANALOG OUTPUTS (OPTION M)
Accuracy:
...............................................±
1% of full scale
Isolation: .............................................................fully isolated active source
OUTPUT RELAYS
Note
This equipment is suitable for use in Class 1, Div 2, Groups A, B, C, D or Non-Hazardous
Locations only if MOD502 is ordered.
Note
Hazardous Location – Class 1, Div 2 output rating if MOD502 is ordered: 240 V, 3 A max,
as per UL1604.
PROGRAMMABLE
OUTPUT
0 to 1 mA
0 to 20 mA 4 to 20 mA
MAX LOAD
2400
Ω
600
Ω
600
Ω
MAX OUTPUT
1.01 mA
20.2 mA
20.2 mA
RESISTIVE LOAD
(pf = 1)
INDUCTIVE LOAD
(pf = 0.4)(L/R –
7ms)
RATED LOAD
8 A at 250 V AC
8 A at 30 V DC
3.5 A at 250 V AC
3.5 A at 30 V DC
CARRY CURRENT
8A
MAX SWITCHING
CAPACITY
2000 VA
240 W
875 VA
170 W
MAX SWITCHING V
380 V AC; 125 V DC
MAX SWITCHING I
8 A
3.5 A
OPERATE TIME
<10 ms (5 ms typical)
CONTACT MATERIAL
silver alloy