background image

GEI-50261 

triangle  as  shown  in  Figure  9 (b). 

In  this  illustration  Vg  represents  the  voltage 

unbalance  of  the  line  voltages. 

The  Vg  voltage  in  this  case  will  be  equal  to 

/3 

VN 

and  therefore  at  pickup: 

For  example,  if  we  wish  the  relay  to  pick  up  when  the  unbalance  represented  by  Vg  is 

20 

volts,  then  we  set  the  relay  to  pick  up  when  a  single-phase  voltage  of 

20 

volts 

is  applied,  shown  in  Figure 

10. 

Consider  an  unbalance  voltage  similar  to  VT 

illustration,  VT  is  the  voltage  shift  in  each 
condition.  Here  VT  is  equal  to  VN,  and  at  pickup: 

shown  1n  Figure  9 (c) . 

In  this 

of  two  corners  from  the  balanced 

Therefore,  if  we  wish  the  relay  to  pick  up  when  the  unbalance  represented  by  VT  is 

10 

volts,  then  the  relay  should  be  set  to  pick  up  when 

/3 

(10) 

17

.

volts. 

CONSTRUCTION 

The  relay  components  are  mounted  in  a  cradle  assembly  that  is  latched  into  a  drawout 
case  when  the  relay  is  in  operation,  but  it  can  be  easily  removed  when  desired. 

To 

do  this,  the  relay  is  first  disconnected  by  removing  the  connection  plug  that 

completes  the  electrical  connections  between  the  case  block  and  the  cradle  block. 

To  test  the  relay  in  its  case,  this  connection  block  can  be  replaced  by  a  test  plug. 

The  cover,  which  is  attached  to  the  front  of  the  relay  case,  contains  an  interlock 
arm  that  prevents  the  cover  from  being  put  back  in  place  until  the  connection  plugs 
have  been  inserted. 

The  relay  case  is  suitable  for  either  semi-flush  or  surface  mounting  on,  all  panels 
up  to 

inches  thick,  and  appropriate  hardware  is  available. 

However,  panel 

thickness  must  be  indicated  on  the  relay  order  to  ensure  that  proper  hardware  will 
be  included.  For  outline  and  drilling  dimensions,  see  Figure 

14. 

Every  circuit  in  the  drawout  case  has  an  auxiliary  brush,  as  shown  in  Figure 

11, 

to 

provide  adequate  overlap  when  the  connecting  plug  is  withdrawn  or  inserted. 

By 

providing  this  overlap,  the  auxiliary  brushes  relieve  the  main  brushes  from  any 

arcing  damage. 

Also,  on  circuits  that  are  equipped  with  shorting  bars  (see  Figure 

8), 

it  is  especially  important  that  the  auxiliary  brush  make  positive  contact  as 

indicated  in  Figure 

11, 

to  prevent  the  opening  of  important  interlock  circuits. 

RECEIVING,  HANDLING 

AND 

STORAGE 

These  relays,  when  not  included  as  part  of  a  control  panel,  will  be  shipped  in 
cartons  designed  to  protect  them  against  damage. 

Immediately  upon  receipt  of  a 

relay,  examine  it  for  any  damage  sustained  in  transit. 

If  1n]ury  or  damage 

resulting  from  rough  handling  is  evident,  file  a  damage  claim  at  once  with  the 

transportation  company  and  promptly  notify  the  nearest  General  Electric  Sales 
Office. 

www 

. ElectricalPartManuals 

. com 

Summary of Contents for 12NBV11A1A

Page 1: ...INGS 4 CALCULATIONS 6 CONSTRUCTION 7 RECEIVING HANDLING STORAGE 7 ACCEPTANCE TESTS 8 INSTALLATION PROCEDURE 10 PERIODIC CHECKS AND ROUTINE MAINTENANCE 10 RENEWAL PARTS 11 TYPE NBVllA GE Protection and Control 205 Great Valley Parkway Malvern PA 19355 1337 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 2: ...BV11A Relay Top View Showing Location of Parts Referred to in Text TELEPHONE RELAY RESISTOR Rl RESISTOR R2 DIODE RECTIFIER BRIDGE Figure 2 8031804 Type NBVl1A Relay Left Side View Figure 3 8031803 Type NBV11A Relay Oblique Rear View 2 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 3: ...e phase condition on light load as well as on heavy load The NBV is usually connected to a bus and it will effectively protect a group of many motors when the open circuit is between the source and the bus As shown in Figure 4 the NBVllA is a high speed relay and a timing relay should be used to prevent false tripping or alarm When undervoltage tripping is permissible the scheme using a 27 device ...

Page 4: ...ll define the relay pickup voltage VR as the single phase voltage that when connected to the relay as shown in Figure 10 will just cause the relay to pick up This will be between 10 and 20 volts for the 120 volt relay and between 17 and 34 volts for the 208 volt relay The corresponding negative phase sequence voltages are 5 8 11 5 for the 120 volt relay and 10 20 for the 208 volt relay The operati...

Page 5: ...potential transformers are connected in open delta as shown in Figure 6 B the burden is as shown in Table III For the best division of burden it is recormnended that terminal No 6 of the relay be connected to the MID point of the delta connected potential transformers TABLE III CURRENT MA VA BURDEN PER P T VOLTS FREQUENCY 15 I6 I7 P T 4fl P T 4f2 120 60 115 38 9 23 4 56 120 50 40 95 66 4 80 7 82 2...

Page 6: ...tages seen by the relay are the same as the relay would see if it were connected to a three phase system that had one phase shorted Thus if we assume v12 is shorted then in equation 1 V1 2 0 v2 3 v2 3 Then equation 1 will reduce to v2 3 3 At Pickup VR J3 VN since VR V2 3 in this case 2 After the amount of unbalance that can be tolerated in the line voltage VN has been determined then the pickup vo...

Page 7: ...he front of the relay case contains an interlock arm that prevents the cover from being put back in place until the connection plugs have been inserted The relay case is suitable for either semi flush or surface mounting on all panels up to 2 inches thick and appropriate hardware is available However panel thickness must be indicated on the relay order to ensure that proper hardware will be includ...

Page 8: ...s With the telephone type relay de energized each normally open contact should have a gap of 010 015 inch Observe the wipe on each normally closed contact by deflecting the stationary contact member towards the frame Wipe should be approximately 005 inch The wipe on each normally open contact should be approximately 005 inch This can be checked by inserting a 005 inch shim between the residual scr...

Page 9: ...wave should decrease Continue increasing resistor R1 until the minimum voltage occurs As the magnitude of the wave decreases it will be due to the fundamental wave decreasing The harmonic content of the wave will remain the same When the point is reached where the fundamental goes to its minimum value if there is much harmonic content in the wave the harmonic wave will predominate If practically n...

Page 10: ...by changing the Resistor R2 setting PERIODIC CHECKS AND ROUTINE MAIRTENANCE In view of the vital role of protective relays in the operation of a power system it is important that a periodic test program be followed It is recognized that the interval between periodic checks will vary depending upon environment type of relay and the user s experience with periodic testing Until the user has accumula...

Page 11: ...required RENEWAL PARTS Sufficient quantities of renewal parts should be kept n stock for the prompt replacement of any that are worn broken or damaged When ordering renewal parts address the nearest Sales Electric Company Specify the name of the part wanted complete nameplate data including the serial number of the the GE requisition number on which the relay was furnished 11 Office of the General...

Page 12: ...9A0254 Potential Transformer Connections for Type NBV11A Relay 0418A0807 2 Test Connections for Checking R C Circuit Adjustment 0418A0805 Internal Connections for Type NBV11A Relay Front View 0459A0252 1 System Voltages under Balanced and Unbalanced Conditions 0459A0223 2 Test Conditions for Setting Pickup of Type NBV11A Relay 8025039 Cross Section of Drawout Case Showing Position of Auxiliary Bru...

Page 13: ...H tt tt r 4 Jt r _ h tt R H H d i t 1 GEI 50261 1 1 ttt t ft i i 1 i t 0 0 0 0 0 t N i Figure 4 SONOJ3Silll Nl 3 11 0459A0251 Operating Times of Type NBVllA Relay Contacts When Unbalanced Voltage Is Suddenly Applied 13 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 14: ... t 1 H 1 0 r M h _4j 1 t tl t i t _ 0 1 0 M _ i t t t r c c I I f c t t tf t _ t t j I fhl l0fi W 1 0 N M SONOJ3Sill1Vi t _ _ t 7 t o t l 1 0 0 M Nl Vi 11 _J_ 1 1 1 t T rq I tt i 0 Figure 5 0459A0250 Operating Times of Type NBVllA Relay Contacts When Unbalanced Voltage Is Suddenly Removed 14 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 15: ...NNECTION FOR WYE CONNECTED P T S l 5 i L 1 0 6 B P T SECONDARIES 7 RELAY S1UDS RECOMMENDED CONNECTION FOR OPEN DELTA P T S Figure 6 0459A0254 Potential Transformer Connections for Type NBVllA Relay 15 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 16: ...GEI 50261 1 t l RATED VOLTAGE 3 FREQUENCY 2 2 3 1 3 9 10 Figure 7 0418A0807 2 Test Connections for Checking R C Circuit Adjustment 16 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 17: ...4 GEI 50261 TR I l i 5 7 6 I I I 111 112 fl j AUTo TRANSFORMER r 9 8 TR 10 x SHORT F I NGER Figure 8 0418A0805 Internal Connections for Type NBVllA Relay Front View 17 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 18: ...TIONS VT 2 b UNBALANCED BY SHIFT OF ONE CORNER c UNBALANCED BY SHIFTING TWO CORNERS b TOWARD EACH OTHER ALONG VECTOR BETWEEN THEM 2 Figure 9 0459A0252 1 System Voltages under Balanced and Unbalanced Conditions 18 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 19: ...AC VARIAC GEI 50261 1 2 4 6 9 COAITI VVITY LIGHT 10 W 7H VOLTA SOVI CI Figure 10 0459A0223 2 Test Connections for Setting Pickup of Type NBV11A Relay 19 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 20: ...E AF TER ENGAGING AUXILIARY B RUSH CONNECTING PLUG TRAVELS Y4 INCH BEFORE ENGAGING THE MAIN BRUSH ON THE TERMINAL B LOCK Figure 11 8025039 Cross Section of Drawout Case Showing Position of Auxiliary Brush 20 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 21: ...760X0 0003 T SI TARGET 1 SEAL IN T D C TIME DELAY CLOS lNG F RA IC FILTER OtS5AS788 I I I I I I I 1 I I PT S I I J I I I j _J_ I J _ II _____ _ WHEII USED r l J o F _ J I 7 5 FUSES IF U f D AUX PT I I RATIO T D C t USE 27 TO TRIP S2 OR 1LARM IF UNDER VOLTAGE TRIPPING I Is PER MISSIBLE USE __ 62 _ TO Tm _52_ OR IlARM IF UNDER VOLTAGE I TRIPPING i IS NOT PERMISSIBLE Figure 12 0459A0253 Sh l 4 Typica...

Page 22: ...0 8 6 4 2 L 29MM I 6 187 1 9MM 3 0 I 157MM 76MM 4 I II I I 4 406 l 112MM I _i_ CUTUUT 8 81 I 224M III 2 843 f 2 M 72MM 1 218 f t ____ 5MM 5 687 PANEL I I II 144MM 5 25 BACK VIEW DRILLED HOLES 1 156 29MM FOR PANEL DRILLING SEMI FLUSH MOUNTING 133MM 3 4 DRILL 10 HOLES 19MM PANEL DRILLING FRONT VIEW FOR SURFACE MOUNTING FRONT VIE 1 TYPICAL DIM INCHES MM Figure 13 6209271 8 Outline and Panel Drilling ...

Page 23: ...I il e I oc3ood 0 0 OG2 GEI 50261 BACK VIEW OF CASE Figure 14 0178A5824 1 Outline and Mounting Dimensions for the Harmonic Filter 23 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 24: ...3 94 200 Protection and Control GE Technology Center 205 Great Valley Parkway Malvern Pennsylvania 19355 1337 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Reviews: