Programming
FireShield Technical Reference Manual
3.11
9. Enter the (DACR1) account code
Description: Sets the account code for DACR1. This is the
code that is used by the monitoring facilities receiver to
identify the panel location and response information. Use a
leading zero to enter a three-digit account code as four digits.
Format: 4 digits
Default: FFFF
To enter the account code:
1. Press Reset until the first digit of the account code is
displayed.
2. Press Panel Silence to save and advance to the next digit.
The trouble buzzer sounds a long beep as confirmation.
3. Press Reset until the next digit is displayed.
4. Press Panel Silence to save and advance to the next digit.
5. Repeat steps 3 and 4 until all digits are entered.
6. When you press Panel Silence at the last digit, the system
automatically advances you to the next program option.
10. Select the DACR1 alarm format
Description: Specifies the type of alarm format the monitoring
facility (DACR) will accept. Selecting either Contact ID or 4/2
loads default event codes (see Appendix E for more
information).
Settings: Contact ID
EST 4/2 (SIA DC-02 P3 with hexadecimal event codes)
Default: Contact ID
To select the DACR1 alarm format:
1. Press Reset to select the desired format.
2. Press Panel Silence to save and advance to the next step.
The trouble buzzer sounds a long beep as confirmation.
11. Select the restore option for CMS one
Description: Determines whether or not restoration events are
sent to the first central monitoring station.
Settings: Send restores
No
restores
Default: Send restores
To select the restore option:
1. Press Reset to select the restore option for CMS one.
2. Press Panel Silence to save.
The trouble buzzer sounds a long beep as confirmation.
12. Enter retry count one
Description: Sets the maximum number of failed attempts to
deliver an alarm to a DACR.
Settings: 5 – 10 retries
Default: 5 (retries)
To enter retry count one:
1. Press Reset to change the retry count.
2. Press Panel Silence to save and advance to the next
program option.
The trouble buzzer sounds a long beep as confirmation.
13. Enter retry time one
Description: Sets the delay time before trying to resend an
alarm to a DACR.
Format: 2 digits max (5 – 10 seconds)
Default: 5 (seconds)
To enter retry time one:
1. Press Reset to enter the retry time.
2. Press Panel Silence to save and advance to the next
program option.
The trouble buzzer sounds a long beep as confirmation.
14. Enter the (DACR2) primary phone number
Note:
If a DACR2 primary phone number is not entered, skip
“Enter the (DACR2) secondary phone number” through
“Enter retry count two,” inclusive.
Description: Specifies the primary phone number that is used
to contact the central monitoring station.
Format: Up to 20 digits
Default: Blank
To enter the primary phone number:
1. Press Reset until the first digit of the phone number is
displayed.
2. Press Panel Silence to save and advance to the next digit.
The trouble buzzer sounds a long beep as confirmation.
3. Press Reset until the next digit is displayed.
4. Press Panel Silence to save and advance to the next digit.
5. Repeat steps 3 and 4 until all digits are entered.
Note:
If less than 20 digits are entered, press Panel
Silence again or Remote Disconnect to advance to the
next program option.
Summary of Contents for FireShield FS1004
Page 1: ...FireShield Technical Reference Manual P N 3100353 Rev 3 0 12MAY03 ...
Page 10: ...System overview and operation 1 8 FireShield Technical Reference Manual ...
Page 40: ...Programming 3 18 FireShield Technical Reference Manual ...
Page 42: ...Maintenance 4 2 FireShield Technical Reference Manual ...
Page 60: ...Panel specifications D 2 FireShield Technical Reference Manual ...
Page 66: ...Index Z 4 FireShield Technical Reference Manual ...
Page 68: ......