FASD700 aspirated smoke detector – Installation manual 

10 

3.2.2  FASD710 / FASD712 functions 

Access the required funtion as described in section 3.1 Selecting and programming 
functions. The relevant LED will flash continuously to indicate the active function. 

Table 1: FASD710 / FASD712 functions 

Function 

Description 

Code entry. See section 3.1.1 Code entry. The Code entry LED 
flashes. 

Set fan speed. The Power LED flashes. 

Set sensitivity of bar graph to changes in airflow velocity. The Flow 
OK LED flashes. 

Select the bar graph LED segment 

above

 which the Flow HI LED 

will be illuminated. The Flow HI LED flashes. 

Select the bar graph LED segment 

below

 which the Flow LO LED 

will be illuminated. The Flow LO LED flashes. 

Select Mains/Battery fault detection. The general Fault LED flashes 
(Mains / Battery LED flashes if selected) 

Calibrate flow sensors at zero and selected airflow speed. The Fan 
fault LED flashes (Fan and Power LEDs flash during calibration). 

Exit function selection and return to normal mode. A 20 second time-
out function will also exit calibration mode. 

 

3.2.3 Unit alarms 

 

Airflow or Power fault (1 relay). 

WWW.UKPANELS.COM

Summary of Contents for FASD700

Page 1: ...GE Security FASD700 aspirated smoke detector installation manual version 3 0 january 2005 WWW UKPANELS COM ...

Page 2: ...ttp www geindustrial com ge interlogix emea 2005 GE Interlogix B V All rights reserved GE Interlogix B V grants the right to reprint this manual for internal use only GE Interlogix B V reserves the right to change information without notice WWW UKPANELS COM ...

Page 3: ...n 5 2 1 Electrical connections 5 2 2 Detector installation 6 2 3 Panel installation 7 2 4 Pipe installation 7 2 5 External connections 7 3 User guide 8 3 1 Selecting and programming functions 8 3 2 FASD710 FASD712 operation 9 3 3 FASD715 FASD717 operation 11 4 Maintenance 14 5 Technical specifications 15 WWW UKPANELS COM ...

Page 4: ...y returned to the sampled area making in ideal for use in small spaces 1 1 2 FASD715 and FASD717 panels FASD715 and FASD717 panels have the following features Two laser detectors supplied in single or two channel configurations This gives a large monitored area using sampling holes in the place of point detectors The FASD717 has two pipes and can cover twice the area of the FASD715 High performanc...

Page 5: ...ectors the inner cover of the panel must be removed Figure 1 PCB connectors for FASD710 FASD712 panels 1 Battery 2 Fault relay 3 Loop in 4 Loop out Figure 2 PCB connectors for FASD715 FASD717 panels 1 Mains power supply left to right earth neutral live 2 Temperature sensor 3 Battery 4 Channel 1 relays left to right fire action fault 5 Channel 2 relays left to right fire action fault 6 External res...

Page 6: ... 1 Remove the panel front cover 2 Connect the loop terminals of the detector s to the 2 way connector block s on the inner panel see Figure 3 Panel detector connection Figure 3 Panel detector connection 2 2 2 Configuration for analogue addressable detectors FASD710 FASD712 A flow fault is reported as a device fault on detector 1 Figure 4 FASD710 FASD712 analogue addressable detector connection 1 T...

Page 7: ... pipe may be used Pipe with an outer diameter of 25 mm or 26 7 mm may be used An adapter is required for used with 25 mm pipe Pipe lengths are cut as required and joined by sockets permanent solvent welded or socket unions removable Smoke tests should be performed before planning and installing the pipe network CAUTION Do not use T joints in low pressure wide bore systems These make pipe design an...

Page 8: ...hange is selected 3 Press and hold the CHANGE key to modify the setting A complete list of available functions for each panel is available in sections 3 2 2 FASD710 FASD712 functions and 3 3 2 FASD715 FASD717 functions 3 1 1 Code entry The code 510 must be entered to allow any function change To enter the code 1 Initialise function selection see above and select the Code entry LED Press change The...

Page 9: ...3 2 FASD710 FASD712 operation 3 2 1 Display LEDs Figure 5 FASD710 FASD712 front panel and display LEDs 1 Power 2 General fault 3 Mains fault 4 Battery low 5 Airflow ok high low 6 Fan fault 7 Bar graph of airflow speed 8 Code entry 9 Unlocked WWW UKPANELS COM ...

Page 10: ...ow velocity The Flow OK LED flashes 4 Select the bar graph LED segment above which the Flow HI LED will be illuminated The Flow HI LED flashes 5 Select the bar graph LED segment below which the Flow LO LED will be illuminated The Flow LO LED flashes 6 Select Mains Battery fault detection The general Fault LED flashes Mains Battery LED flashes if selected 7 Calibrate flow sensors at zero and select...

Page 11: ...isplay LEDs The FASD715 FASD717 panels use the same interface and LEDs as the FASD710 FASD712 panels see Figure 5 with the following additions Figure 6 FASD715 FASD717 front panel and display LEDs 1 Alert alarm 2 Action alarm 3 Fire alarm 4 Smoke detector fault 5 Isolate 6 Reset WWW UKPANELS COM ...

Page 12: ...The Flow HI LED flashes 7 Select the bar graph LED segment below which the Flow LO LED will be illuminated The Flow LO LED flashes 8 Set smoke detector ALERT alarm threshold The Alert LED flashes 9 Set smoke detector ACTION alarm threshold The Action LED flashes 10 Set smoke detector FIRE alarm threshold The Fire LED flashes 11 Select Mains Battery fault detection The general Fault LED flashes Mai...

Page 13: ...e level of smoke being detected Table 3 shows how the levels on the bar graph correspond to the smoke levels being detected These are also the levels at which the alarms can be set Table 3 Bar graph levels Bar graph LED Obscuration metre 1 0 065 2 0 098 3 0 164 4 0 327 5 0 655 6 1 637 7 3 273 8 4 887 9 6 516 WWW UKPANELS COM ...

Page 14: ...t cartridge enabling rapid inspection and maintenance The lifespan of the filter will depend on the installation environment A dirty filter will reduce airflow and lower the accuracy of smoke detection To change the filter 1 Remove the panel cover 2 Remove the filter from the acrylic housing 3 Insert the new filter 4 Replace the panel cover WWW UKPANELS COM ...

Page 15: ...reporting Supply voltage 24 VDC Supply current without aspirating pipe 460 mA Supply current Dependant on fan speed pipe length See Table 4 Maximum pipe length per channel 100 m IP rating IP50 IP65 optional Operating temperature 10 to 60ºC Operating humidity 10 to 95 RH non condensing Table 4 Fan speed supply current with 20 m pipe length and 6 mm end hole Fan speed Supply current mA 9 330 8 260 7...

Page 16: ... 1052955 WWW UKPANELS COM ...

Reviews: