B-8
L60 Line Phase Comparison System
GE Multilin
B.3 FILE TRANSFERS
APPENDIX B
B
e) READING DATA LOGGER FILES
Familiarity with the data logger feature is required to understand this description. Refer to the Data Logger section of Chap-
ter 5 for details. To read the entire data logger in binary COMTRADE format, read the following files.
datalog.cfg
and
datalog.dat
To read the entire data logger in ASCII COMTRADE format, read the following files.
dataloga.cfg
and
dataloga.dat
To limit the range of records to be returned in the COMTRADE files, append the following to the filename before writing it:
•
To read from a specific time to the end of the log: <space> startTime
•
To read a specific range of records: <space> startTime <space> endTime
•
Replace <startTime> and <endTime> with the number of seconds since Jan. 1 1970 as numeric text
f) READING EVENT RECORDER FILES
To read the entire event recorder contents in ASCII format (the only available format), use the following filename:
EVT.TXT
To read from a specific record to the end of the log, use the following filename:
EVTnnn.TXT
(replace
nnn
with the desired starting record number)
To read from a specific record to another specific record, use the following filename:
EVT.TXT xxxxx yyyyy
(replace
xxxxx
with the starting record number and
yyyyy
with the ending record number)
g) READING FAULT REPORT FILES
Fault report data has been available via the L60 file retrieval mechanism since UR firmware version 2.00. The file name is
faultReport#####.htm
. The ##### refers to the fault report record number. The fault report number is a counter that
indicates how many fault reports have ever occurred. The counter rolls over at a value of 65535. Only the last ten fault
reports are available for retrieval; a request for a non-existent fault report file will yield a null file. The current value fault
report counter is available in “Number of Fault Reports” Modbus register at location 0x3020.
For example, if 14 fault reports have occurred then the files
faultReport5.htm
,
faultReport6.htm
, up to
faultReport14.htm
are available to be read. The expected use of this feature has an external master periodically poll-
ing the “Number of Fault Reports' register. If the value changes, then the master reads all the new files.
The contents of the file is in standard HTML notation and can be viewed via any commercial browser.
Summary of Contents for L60
Page 10: ...x L60 Line Phase Comparison System GE Multilin TABLE OF CONTENTS ...
Page 57: ...GE Multilin L60 Line Phase Comparison System 2 27 2 PRODUCT DESCRIPTION 2 3 SPECIFICATIONS 2 ...
Page 58: ...2 28 L60 Line Phase Comparison System GE Multilin 2 3 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 482: ...6 26 L60 Line Phase Comparison System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 554: ...10 8 L60 Line Phase Comparison System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Page 674: ...B 110 L60 Line Phase Comparison System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 704: ...C 30 L60 Line Phase Comparison System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 720: ...E 10 L60 Line Phase Comparison System GE Multilin E 1 PROTOCOL APPENDIX E E ...
Page 732: ...F 12 L60 Line Phase Comparison System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 742: ...H 8 L60 Line Phase Comparison System GE Multilin H 3 WARRANTY APPENDIX H H ...