background image

Fig 3. GDS-IR / LPI FIELD WIRING 

Apply  power  to  the  GDS-IR  /  LPI  and  allow  the 

instrument to stabilize for at least one (1) hour.  

IMPORTANT - Ensure there is no combustible 

gas present during the auto-zero procedure. 

Apply a flow of nitrogen or known ‘zero air’ if 

necessary.  Setting zero with background target 

gas will cause erroneous readings.  

Using a magnetic wand, activate the auto-zero switch 

located behind the RED conduit end-cap on the Loop 

Powered Display enclosure. Hold the wand in place 

for at least 10 seconds, but not more than 20 

seconds. The GDS-IR should momentarily output 

2.2mA to indicate a successful auto-zero. The LPI 

numeric display may dim or disappear momentarily. 
Adjust the ZERO setting on the LPI until the display 

reads “00.0”.  
Apply a 0.5 to 1.0 LPM flow of 50% LEL methane 

calibration gas to the GDS-IR via the 1/4” inlet 

located on the bottom of the instrument. When 

stabilized, adjust the SPAN setting on the LPI to read 

“50.0”. 
Remove the calibration gas and recheck for zero. 

The instrument is now ready for operation.  

INITIAL STARTUP & AUTO ZERO 

During normal operation*, the output of the GDS-IR 

current loop continuously indicates the concentration 

of combustible hydrocarbon gas present in the 

ambient atmosphere. In the event of instrument 

malfunctions or calibration activities, the output 

current value can be used to determine status as 

shown: 

OPERATION 

TB1 

GDS-IR 

LPI 

+18-32VDC 

COMMON 

4-20mA OUT 

Red 

Black 

Blue 

White 

Auto Zero 

0.0mA 

Instrument Fault 

2.2mA 

Unit Zeroing 

0.2mA 

Ref Channel Fault  4.0mA 

Zero Gas 

0.4mA 

Analytic Ch Fault 

5.6mA 

10% LEL* 

0.8mA 

Unit Warm-Up 

8.0mA 

25% LEL* 

1.0mA 

Optics Fault 

12mA 

50% LEL* 

1.2mA 

Zero Drift Fault 

16mA 

75% LEL* 

1.6mA 

Calibration Fault 

20mA 

100% LEL* 

2.0mA 

Unit Spanning 

20 - 23mA  Over-range 

CLEANING 

To inspect or clean the optics path, unscrew the 

barrel of the GDS-IR. Remove the slotted setscrew 

and hydroscopic filter. Loosen the small hex 

setscrew on the center assembly and remove the 

assembly by rotating the long barrel CW and the top 

fitting CCW. Clean the upper and lower optics 

windows using lint-free cloth. Reassemble in 

reverse order. 
After cleaning, always perform the auto-zero 

operation as described above.  

Note: 

The Loop Powered 

Indicator will NOT operate 

unless the 4-20mA current 

loop output (TB1-5) is 

connected to COMMON at the 

receiving instrument input 

Reviews: