Parameter definations and settings
16
SETTINGS: Touch function over 3 seconds – hear a sound – off your hand – enter your settings.
Code Parameter
Range
Standard setting
/ / /
Water tank temperature setting
20 °C – 60 °C
35 °C / 45 °C / 50 °C / 55 °C
L1
Dummy temperature
0 °C – 15 °C
00 °C
L2
Compressor start & set temperature
3 °C – 18 °C
05 °C
L3
Set outlet water temperature
35 °C – 99 °C
35 °C / 45 °C / 50 °C / 55 °C
L4
Maximal water tank temperature
30 °C – 99 °C
60 °C
L5
Electric start temperature
0 °C – 35 °C
00 °C
(0 °C mean no electric assistant heater)
L6
Return water temperture
30 °C – 65 °C
30 °C / 40 °C / 45 °C / 50 °C
L7
Supplement water temperature
20 °C – 60 °C
20 °C
(20 °C mean no supplemmet)
L8
Compressor current
0 – 48A
0
H1
Defrosting period
20 min. – 99 min.
35 min.
H2
Permission temperature for defrosting
-15 °C – 1 °C
-01 °C
H3
Defrosting time
5 – 20 min.
10 min.
H4
Defrosting temperature
1 °C – 40 °C
20 °C
P1
Electric expansion valve adjust period
20 – 180 sec.
30 sec.
P2
Difference temperature between A1 and A2
-8 °C – 15 °C
00 °C
P3
Pemission for exhaust temperature protection
70 °C – 135 °C
95 °C
P4
Electric expansion valve open angel
when defrosting
6 – 55 degree
50 degree
P5
Electric expansion valve minimal open angel
6 – 30degree
15 degree
Summary of Contents for Eco Air Split series
Page 1: ...Installation and Operating Instructions GDH Eco Air Split series ...
Page 4: ...Components 4 ...
Page 5: ...Connection Indoor and Outdoor Unit 5 ...
Page 6: ......
Page 7: ...House Installation 7 ...
Page 8: ...Hydraulic Connection 8 ...
Page 10: ...Electrical Wire Diagram 10 ...
Page 19: ...19 ...
Page 21: ...21 ...
Page 23: ...23 ...