5.10 Advanced Func�on Setup Menu

5.9 Generator  Port Use Setup Menu

Generator input rated power:

 allowed Max. power from diesel 

generator.

GEN connect to grid input:

 connect the diesel generator to the 

grid input port.

Smart Load Output: 

This mode u�lizes the Gen input connec�on 

as an output which only receives power when the ba�ery SOC 

is above a user programmable threshold. 

e.g.  ON: 100%, OFF=95%:

 When the ba�ery bank SOC reaches 

100%, Smart Load Port will switch on automa�cally and power 

the load connected. When the ba�ery bank SOC < 95% , the 

Smart Load Port will switch off automa�cally. 

Smart Load OFF Ba�

• Ba�ery SOC at which the Smart load will switch off.

Smart Load ON Ba�

•  Ba�ery SOC at which the Smart load will switch on. simultaneously and then the Smart load will switch on. 

On Grid always on:

 When click "on Grid always on" the smart load will switch on when the grid is present.

Micro Inv Input:

 To use the Generator input port as a micro-inverter on grid inverter input (AC coupled), this feature will 

also work with "Grid-Tied" inverters. 

Micro Inv Input OFF: when the ba�ery SOC exceeds se�ng value, Microinveter or grid-�ed inverter will shut down.

Micro Inv Input ON: when the ba�ery SOC is lower than se�ng value, Microinveter or grid-�ed inverter will start to 

                                        work.

AC Couple Frz High: 

If choosing“Micro Inv input”, as the ba�ery SOC reaches gradually se�ng value (OFF), During the 

process, the microinverter output power will decrease linear. When the ba�ery SOC equals to the se�ng value (OFF), 

the system frequency will become the se�ng value (AC couple Frz high) and the Microinverter will stop working.

MI export to grid cutsoff:  Stop expor�ng power produced by the microinverter to the grid.

Note: Micro Inv Input OFF and On is valid for some certain FW version only. 

Solar Arc Fault ON

Clear Arc_Fault

System selfcheck

BMS_Err_Stop

CEI Report

0s

2000

1

Backup Delay

Advanced Function

Func

Set1

DRM

Gen peak-shaving

CT Ratio

Signal Island Mode

Asymmetric phase feeding

Solar Arc Fault ON:

 

This is only for US.

System selfcheck:

 Disable. this is only for factory.

Gen Peak-shaving: 

Enable When the power of the 

generator exceeds the rated value of it, the inverter will 

provide the redundant part to ensure that the generator 

will not overload.

DRM: 

For AS4777 standard

Backup Delay: 

Reserved

BMS_Err_Stop: 

When it is ac�ve, if the ba�ery BMS failed 

to communicate with inverter, the inverter will stop 

working and report fault.

L1 L2 L3 N

Load port 

Inverter

Shell

 Relay

Ground cable

Signal island mode:

  If "Signal island mode" is checked and When inverter is in off-grid mode, the relay on 

the Neutral line (load port N line) will switch ON then the N line (load port N line) will bind to inverter ground.

Asymmetric phase feeding:

  If it was checked, the excess PV energy that feeds into the grid will be balanced 

on the three phase.

Mode

OFF(V)

ON(V)

Generator Input

SmartLoad Output

Micro Inv Input

On Grid always on

GEN connect to Grid input

Ml export to Grid cutoff

GEN PORT USE

55.00Hz

54.0V

51.0V

Rated Power

AC Couple Frz High

8000W

PORT

Set1

Summary of Contents for RY-12K-AUP3

Page 1: ...07 08 2021 11 11 10 Thu 76 2 00 KW 1 39 KW 0 00 KW KW 0 7 0 5 0 5 0 5 ON Signal on 2 00 Hybrid Inverter User Manual RY 12K AUP3...

Page 2: ...cation diagram of diesel generator 3 10 Wiring diagram 3 12 phase parallel connection diagram 6 Mode 38 39 5 6 Battery Setup Menu 5 7 System Work Mode Setup Menu 5 8 Grid Setup Menu 5 9 Generator Port...

Page 3: ...u want to disconnect AC or DC terminals Please refer to Installa on sec on of this manual for the details Grounding instruc ons this inverter should be connected to a permanent grounded wiring system...

Page 4: ...el port 7 Meter 485 port 8 Ba ery input connectors 9 Func on port 10 ModeBUS port 11 BMS port 12 PV input with two MPPT 13 Circuit breaker of Grid 15 Generator input 14 Load 16 WiFi Interface 17 DRM p...

Page 5: ...03 2 2 Product Size Inverter Size Moun ng bracket...

Page 6: ...mart Load Func on 2 4 Basic System Architecture 2 5 Maintenance of the System The following illustra on shows basic applica on of this inverter It also includes following devices to have a Complete ru...

Page 7: ...ave received the items in the following package Wall moun ng bracket x1 Hybrid inverter x1 Parallel communica on cable x1 L type Hexagon wrench x1 Stainless steel an collision bolt M8 80 x4 User manua...

Page 8: ...elevision Antenna or antenna cable Not higher than al tude of about 2000 meters above sea level Not in environment of precipita on or humidity 95 Considering the following points before selec ng where...

Page 9: ...e careful when li ing out from the package Choose the recommend drill head as shown in below pic to drill 4 holes on the wall 82 90mm deep 1 Use a proper hammer to t the expansion bolt into the holes...

Page 10: ...ed between the ba ery and the inverter In some applica ons switching devices may not be required but over current protectors are s ll required Refer to the typical amperage in the table below for the...

Page 11: ...h a suitable cable is important for safe and e cient opera on of the system To reduce the risk of injury refer to Chart 3 2 for recommended cables All wiring must be performed by a professional person...

Page 12: ...Temp CT 11 1 2 3 3 3 Temperature sensor connec on for lead acid ba ery Inverter...

Page 13: ...ry contact output When the inverter is in o grid mode and the signal island mode is checked the dry contact will switch on Grid_Ry 5 6 reserved RSD 7 8 When ba ery is connected and the inverter is in...

Page 14: ...y disconnected during maintenance and fully protected from over current The recommended of AC breaker for the load port is 32A for 12KW The recommended of AC breaker for the grid port is 63A for 12KW...

Page 15: ...nec ng to PV modules please install a separately DC circuit breaker between inverter and PV modules It is very important for system safety and e cient opera on to use appropriate cable for PV module c...

Page 16: ...panel is not connected to the system ground bar Safety Hint Before connec ng inverter please make sure the PV array open circuit voltage is within the 800V of the inverter Note This inverter complies...

Page 17: ...re listed as follows a Strip o the DC wire about 7mm disassemble the connector cap nut see picture 5 3 b Crimping metal terminals with crimping pliers as shown in picture 5 4 c Insert the contact pin...

Page 18: ...Pic 3 6 DC input connec on Warning Sunlight shines on the panel will generate voltage high voltage in series may cause danger to life Therefore before connec ng the DC input line the solar panel needs...

Page 19: ...nec on White wire 5 4 3 6 7 8 Black wire Grid N R S T CT1 CT2 CT3 GRID N R S T PE CT Arrow pointing to inverter Note when the reading of the load power on the LCD is not correct please reverse the CT...

Page 20: ...ter Three Phase Smart Meter SET ESC 1 7 4 10 25 24 3 9 6 10 RS 485 CHNT DTSU666 3 6 9 10 1 4 7 10 R S T Grid Inverter R R S S T T N N Parallel_A Parallel_B Meter 485 port RS485A RS485B Grid Eastron me...

Page 21: ...be connected to ground plate on grid side this prevents electric shock if the original protec ve conductor fails Note When the inverter is in the o grid state the N line needs to be connected to the...

Page 22: ...BAR E N Link Grid Battery BMS DC Breaker PV DC Breaker This diagram is an example for an applica on that neutral connects with the PE in a distribu on box For countries such as Australia New Zealand S...

Page 23: ...C Breaker AC Breaker AC Breaker Battery pack Home Load R R S S T T N N PE PE R S T N PE DC Breaker for battery RY 12K AUP3 300A DC breaker AC Breaker for backup load RY 12K AUP3 32A AC breaker AC Brea...

Page 24: ...erator 1 2 GS diesel generator startup signal relay coil open contact G S G start 1 2 dry contact signal for startup the diesel generator Remotely control signal line RY 12K AUP3 300A DC breaker DC Br...

Page 25: ...Slave Inverter Slave Inverter EX_Meter For CT Meter Select 0 3 No Meter 01 Parallel_A Parallel_B Meter 485 Grid CT1 CT2 CT3 Backup Load Inverter No 3 slave Inverter No 2 slave Inverter No 1 master Gr...

Page 26: ...e selec on 24 Once the unit has been properly installed and the ba eries are connected well simply press On O bu on located on the le side of the case to turn on the unit When system without ba ery co...

Page 27: ...bu on you can enter into the system setup screen which including Basic Setup Ba ery Setup Grid Setup System Work Mode Generator port use Advanced func on and Li Ba info 4 The main screen showing the...

Page 28: ...in Screen Solar Page Solar Graph Grid Graph BMS Page Load Graph Battery Setting System Work Mode Grid Setting Gen Port Use Basic Setting Advanced Function Device info Grid Page Inverter Page Battery P...

Page 29: ...Battery PV1 PV2 Grid Inverter Today 0 5 KWH Total 1 60 KWH L1 220V P1 19W L2 220V P2 18W L3 220V P3 18W Load Energy This is Back up Load detail page Press the Energy bu on will enter into the power c...

Page 30: ...ar Total System Grid Power Total CANCEL Day Month Year Total Mean Voltage 50 34V Charging Voltage 53 2V Total Current 55 00A Discharging Voltage 47 0V Mean Temp 23 5C Charging current 50A Total SOC 38...

Page 31: ...s Factory Reset 2019 03 09 15 17 Factory Reset Reset all parameters of the inverter Lock out all changes Enable this menu for se ng parameters that require locking and cannot be set up Before performi...

Page 32: ...es the Ba ery Grid Charge It indicates that the grid charges the ba ery This is Grid Charge you need select Batt Mode Lithium Use Batt V Battery Setting Activate Battery Max A Charge Batt Capacity Max...

Page 33: ...is BMS protocol Please reference the document Approved Ba ery Shutdown 10 It indicates the inverter will shutdown if the SOC below this value Low Ba 20 It indicates the inverter will alarm if the SOC...

Page 34: ...ckup load connected The hybrid inverter will neither provide power to the home load nor sell power to grid The built in CT will detect power owing back to the grid and will reduce the power of the inv...

Page 35: ...00 05 00 08 00 10 00 15 00 18 00 5 00 8 00 10 00 15 00 18 00 01 00 Power 80 40 40 80 40 35 Work Mode2 For example Solar Sell Solar sell is for Zero export to load or Zero export to CT when this item i...

Page 36: ...l be reset to their default values for Australia RegionA B C respec vely Grid Mode General Standard UL1741 IEEE1547 CPUC RULE21 SRD UL 1741 CEI 0 21 Australia A Australia B Australia C EN50549_CZ PPDS...

Page 37: ...adjust inverter reac ve power FW this series inverter is able to adjust inverter output power according to grid frequency Droop F percentage of nominal power per Hz For example Start freq F 50 2Hz Sto...

Page 38: ...s less than 5 rated power the VQ mode will not take e ect Lock out Pn 20 If the inverter ac ve power is increasing from 5 to 20 rated power the VQ mode will take e ect again For example V2 110 P2 80 W...

Page 39: ...er will decrease linear When the ba ery SOC equals to the se ng value OFF the system frequency will become the se ng value AC couple Frz high and the Microinverter will stop working MI export to grid...

Page 40: ...52 0 26 0Ah 0 0V 0 0A 0 0 0 50 33V 19 10A 31 0C 51 0 25 5Ah 53 2V 25 0A 0 0 0 50 30V 16 90A 30 2C 12 0 6 0Ah 53 2V 25 0A 0 0 0 4 5 0 00V 0 00A 0 0C 0 0 0 0Ah 0 0V 0 0A 0 0 0 0 00V 0 00A 0 0C 0 0 0 0A...

Page 41: ...cannot and can only legally exclude all liability within a limited scope 39 The 1st priority power of the system is always the PV power then 2nd and 3rd priority power will be the ba ery bank or grid...

Page 42: ...nute and then turn on the DC AC switch 6 Seek help from us if can not go back to normal state AC side over current fault 1 Please check whether the backup load power and common load power are within t...

Page 43: ...re firmly and correctly connected 3 Seek help from us if can not go back to normal state F29 Parallel CAN Bus fault 1 When in parallel mode check the parallel communication cable connection and hybrid...

Page 44: ...mmunication between hybrid inverter and battery BMS disconnected when BMS_Err Stop is active 2 if don t want to see this happen you can disable BMS_Err Stop item on the LCD 3 If the fault still exists...

Page 45: ...e to the following reasons Damage during transporta on of equipment Damage caused by incorrect installa on or commissioning Damage caused by failure to comply with opera on instruc ons installa on ins...

Page 46: ...RY 12K AUP3 240A 240A 15600W 39A 19 5A 26A 13A 12000 12000 Rated AC Output and UPS Power VA Max AC Current A 17 4A 17 4A Max Con nuous AC Passthrough A 97 60 E ciency Max E ciency 97 00 Euro E ciency...

Page 47: ...ansport inverter Usually placed inverter in the packing box with tape sealing if the inverter cannot reoccupy you can choose a cheap carton for packaging Carton requirements must meet the size of the...

Page 48: ...5 6 7 8 METER 485_B Meter 485 Pin METER 485_A COM GND COM GND METER 485_A METER 485_B 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 BMS Port Meter 485 Port 1 2 3 4 5 6 7 8 87 65 43 21 87 65 43 21 Modbus port 1 2 3...

Page 49: ...used to connect the wi datalogger DRM port 1 2 3 4 5 6 7 8 87 65 43 21 1 No 2 3 4 5 6 7 8 DRM1 5 NetJ4_7 Modbus port DRM2 6 DRM3 7 D GND DRM4 8 REF GEN 0 NetJ4_7 De ni on of RJ45 Port Pin for DRM Port...

Page 50: ...Ver 2 2 2023 02 16 48 1 Split Core Current Transformer CT dimension mm 2 Seconddary output cable length is 4m 12 Appendix II Lead Outside...

Page 51: ......

Reviews: