Guangcheng Technology
GC-3804 user manual
3. Technical specifications
Connection method
Wiring form
2-wire system
Interface characteristics
Input points
4
sensor type
PT100
temperature range
-200~+500
℃
Resolution
0.1
℃
/digital
Conversion time
<
250 ms
Measuring current
0.5 mA
Measurement error
<
±2℃
Electrical isolation
500 Vrms (GC-bus/signal voltage)
Power supply
Powered by GCAN-PLC-400 or
GCAN-8000/8100 coupler, the current
consumption is more than 200mA
Bit width in process image
Input: 4 x2 bytes
Configuration method
Automatic configuration in order
Environmental test
Operating temperature
-40
℃
~+85
℃
Working humidity
95%RH, no condensation
EMC test
EN 55024:2011-09
EN 55022:2011-12
Anti-vibration/impact
resistance
EN 60068-2-6/EN 60068-2-27/29
Anti-electromagnetic
interference/anti-electromag
netic radiation performance
EN 61000-6-2 /EN 61000-6-4
Protection level
IP 20
Basic Information
Dimensions
100mm *69mm *12mm
weight
50g