For more information & technical support:
30
F-Guard UV-IR-HD User Manual
76-M-6010-02-02
9. Specifications
Fire Detection
•
Detection time and distance:
o
40ms
-
for fast fire burst or explosion
o
1.5s
-
for 1ft
2
(0.1m
2
) N-heptane pan fire at 100 ft (30m)
o
4s
-
for 1ft
2
(0.1m
2
) N-heptane pan fire at 230 ft (70m)
•
Field of view: 90° Horizontal, 75° Vertical
•
Time Delay: 0-30 seconds (adjustable)
•
Built-in test: Automatic and Manual
Video Functionality
•
HD Video allowing clear imaging of fire and people at 100ft. (30m) distance.
•
Video recording of alarm events 1 minute before and up to 3 minutes after the flame is
detected.
•
System integration protocol: ONVIF (Open Network Video Interface Forum) Profile S
Electrical Specifications
•
Operating Voltage: 24 VDC nominal (18-32 VDC)
•
Current Consumption:
o
Standby
180mA
o
Maximum
300mA all systems in operation (including window heater)
•
Cable Entries: 2x conduit entries 3/4” NPT or M25, with one entry plugged with a suitably
certified stopper.
•
Wiring: 14-17AWG (2.5-1.0mm
2
)