76-M-6010-02-02
F-Guard IR3 HD User Manual
3 Configuration options
Some functions of the detector can be configured using an RS-485 modem connected to
a computer with the “
Gastech
communicator” software. For details of how to download
the software please contact technical support via email at [email protected]
.
These configuration options are listed in the following table along with their factory
default values.
T
ABLE
2:
D
ETECTOR
C
ONFIGURATION
O
PTIONS
Function
Options
Default Setting
Sensitivity
Very low, Low, Medium, High,
Extreme
Medium
Ultra-fast detection
Disabled, Enabled
Disabled
Alarm Delay
0, 5, 10, 20 or 30 seconds
0 seconds (no
delay)
Alarm Latch
Disabled, Enabled
Disabled
Video module
Disabled, Enabled
Enabled
Video analog output
Disabled, NTSC, PAL
Disabled
Enable Pre-Alarm 0-20mA
Disabled, Enabled
Disabled
Enable dirty window warning 0-
20mA
Disabled, Enabled
Disabled
Aux. Relay
Alarm
Pre-Alarm
Dirty Window Warning
Alarm
Window Heater
Disabled, Enabled
Enabled
Modbus address
1 – 247
1
Manual BIT – Alarm Output Test Disabled, Enabled
Disabled
•
Note:
Medium sensitivity setting allows detection of a 1x1ft
2
(0.1m
2
) N-
heptane pan fire at a distance of 100ft (30m).