GasSecure GS01
Hardware Manual
MAINTENANCE
27
information. The “Diag_Status” attribute provides the information as outlined in
Table 5-2.
If multiple warnings or errors occur, always clear battery warning or error first by
replacing the battery pack (cf. Section 5.4.1).
For failures (mode F) not explained in Table 5-2, please clean window and mirror
(cf. Section 5.3). If the failure persists, contact GasSecure.
Table 5-2: Status messages retrieved from the Diag_Status attribute
Instrument
mode
(cf. Table 10-2)
DIAG_STATUS
bit set
(cf. Table 10-2)
Explanation and actions
M
19
Low battery.
The battery must be replaced.
F and M
20
Empty battery.
Replace battery immediately (see Section 5.4).
M
7
Attenuated optical beam (low
optical
transmission).
The instrument detects low light transmission
and infrared signal strength most probably due
to dirty optics. Clean the window and mirror if
necessary (cf. Section 5.3). The status
message will clear within 10 minutes.
F and M
8
Beam block (optical beam fault).
The signal is so weak that the gas
concentration cannot be calculated with
sufficient accuracy, or the beam intensity is
changing rapidly.
Check for dirty optics and clean the window
and mirror (cf. Section 5.3) if necessary.
O
22
The system temperature is outside the
specified operating range. For repeated high
temperature warnings the use of a sunshade
should be considered.
F, O, and M
22 and 8
Process value under-range.
Clean the window and mirror (cf. Section 5.3).
If the error persists, contact GasSecure.
5.7
Contact GasSecure for support
You will find our contact information and an updated list of our representatives on
our homepage
www.gassecure.com