background image

4  Wiring Instructions 

4.1, Cable requirements:

Power lines and 4-20mA signal lines need to use shielded cables, and RS485 lines are recommended to 

use twisted pairs. When using RS485 communication to connect with the controller (Under normal 

conditions) , the RS485 signal transmission distance of our detector can reach more than 1000 meters. 

When the signal interference is large or the transmission distance is longer, it is recommended to add an 

RS485 repeater, a 120Ω/0.5W matching resistor should be connected in parallel between the A and B lines 

of the farthest detector.

The power supply voltage of this series of detectors is 12~24VDC. Due to the voltage drop caused by the 

impedance of the cable itself, it should be ensured that the minimum supply voltage of all detectors is 

12VDC.

When  the  detector  is  powered  by  the  controller,  the  power  supply  voltage  of  the  controller  of  our 

company  is  24VDC.  To  ensure  that  the  minimum  input  voltage  of  the  detector  is  12VDC,  the  circuit 

voltage drop must be less than or equal to 12VDC, as shown in the figure below.

Maximum Loop Impedance: Rloop = (VController – VDetector(min)) / IDetector 

Calculated 

according to the above formula.

The maximum current of combustible gas detector is 250mA, and the maximum loop resistance is 

48Ω;

The maximum current of the toxic gas detector is 100mA, and the maximum loop resistance is 120Ω.
The cable cross-sectional area and the farthest transmission distance are shown in the table below 

(when  connected  to  our  controller).  Make  sure  that  the  actual  installed  cable  length  is  shorter  than  the 

calculated maximum cable transmission distance.

4-20mA

Maximum Loop Resistance

V Controller=24VDC

V Controller=12VDC

Gas detector

Controller

0VDC

0VDC

1

2

3

3

2

1

RL

Cross-sectional area of cable core (mm )

0.75

1.00

1.50

2.50

Resistance (ohm/km copper wire)

24.7

18.5

12.3

7.4

The longest cable distance (m)

(loop length/2)

Combustible gas

1000

1250

2000

3200

Toxic gas

2400

3200

5000

8000

Note: The above transmission distance is calculated based on the cable core with a resistivity of 

1.85×10ˉ  Ω·mm . If a cable of the same wire diameter with a smaller resistivity than this is used, the 

transmission distance can be longer; if a cable of the same wire diameter with a higher resistivity than this is 

used, the transmission distance will be shortened. The loop length indicates the total length of the positive 

and negative wires of the power supply, and the actual length of the cable is equal to half of the loop length.

7

www.gasdog.com

[email protected]

+86 773-280-9002

Summary of Contents for GD300 Series

Page 1: ...Online Fixed Gas Detector GD300 XX Instruction Manual Notice to Reader Please read this instruction manual before using the detector 1 www gasdog com sales gasdog com 86 773 280 9002...

Page 2: ...ery 3 6 months the explosion proof disc of the sensor should be cleaned regularly purging with low pressure compressed air according to the applicable scene otherwise dust and impurities will block th...

Page 3: ...re operation 2 Structure diagram 3 Installation method 4 Wiring Instructions 5 Calibration method 6 Remote controller operation 7 Common faults and repairs 8 Instrument con guration 9 Appendix 3 www g...

Page 4: ...many alarms or the long term alarm state will make people paralyzed if it is too far the reaction speed will be too slow or even no response B The instrument should be installed in the downwind direc...

Page 5: ...ype The installation thread size of the instrument is M45 P2 0 During the installation process hold the detector with both hands so that the sensor is parallel to the installation thread align the scr...

Page 6: ...rance and installation hole map 118 00 8 00 140 00 8 00 8 00 102 30 206 00 89 00 Apperance and installation hole map of gas detector with alarm light 8 00 179 00 102 00 8 00 8 00 118 00 206 00 89 00 6...

Page 7: ...mula The maximum current of combustible gas detector is 250mA and the maximum loop resistance is 48 The maximum current of the toxic gas detector is 100mA and the maximum loop resistance is 120 The ca...

Page 8: ...the load resistance which includes the output resistance of the control system controller DCS or PLC and the internal resistance of the cable Cable distance m 100 200 500 1000 The maximum allowable n...

Page 9: ...needs to open the instrument shell and connect wires to the inside terminals The following gure is the description of each terminal Warning The wiring work must be performed by professionals otherwis...

Page 10: ...the alarm settings of the detector and the panel are adjusted to the factory default values and the user can adjust it through the remote controller according to the situation Zero calibration Make su...

Page 11: ...zero calibration is successful it will automatically return to the detection interface IR ALAH Span calibration Connect the calibration gas cylinder of known concentration to the calibration cap Opti...

Page 12: ...i ed by the and keys to make the value consistent with the calibration gas concentration Press the OK key to display PASS brie y IR ALAH IR ALAH IR ALAH IR ALAH IR ALAH IR ALAH 2 Press the key to disp...

Page 13: ...ting menu press the OK key to enter the modi cation press the and keys to modify the instrument address code and press the OK key to save after the modi cation is completed Press the BACK key to cance...

Page 14: ...value Calibration after stable reading in clean environment F 05 4MA current trimming C 04 4mA output modi able C 08 8mA output cannot be modi ed C 12 12mA output cannot be modi ed C 16 16mA output c...

Page 15: ...ot enough warm up time Sensor failure Circuit failure Send back for repair recalibrate Reset the detector range Replace the sensor recalibrate Reset the detector range Replace the sensor Power on and...

Page 16: ...tively These two signal output modes are also di erent when wiring A 4 20mA current signal output connection mode must be grounded together B RS485 digital signal output connection mode 1 can be indep...

Page 17: ...C RS485 digital signal output connection mode 2 can be independently grounded RS485B RS485A GND PC software RS485 to USB 1 2 N 24V DC GND 17 www gasdog com sales gasdog com 86 773 280 9002...

Reviews: