background image

 Gas Detection (Australia) Pty Ltd 

Page 8 of 12 

M-3160-003-1     05/12/2017

 

Refrigerant Gas Relay Alarm Point Formula: 

Vin = Alarm point Concentration / 204.8 

Example; 
Alarm level set point required at 250ppm  
250/204.8= 1.22 V 
1.

 

The alarm switch point is preset with 10% hysteresis to prevent relay “chatter”; 

 

2.

 

The relay is non-latching and will turn off when the gas level falls to below 10% of the alarm point; and

 

3.

 

The alarm relay contacts are rated 50 V

DC

 0.5 A non inductive. If heavier loads require switching a slave 

relay must be used.

 

 

Calibration: 

The GDA 3160 are factory calibrated to 0-1000ppm of the users required target gas and are sent out with 
a certificate of calibration stating target gas information. 
  
Functional testing may be carried out with a suitable test gas to ensure that the 4-20ma o/p corresponds 
with the gas level. This should be undertaken when the unit is fully assembled and using a flow rate of 
~0.5L/min of the target gas. Test gas and equipment are available from Gas Detection Australia.  
    
When in service, if the sensor falls below a minimum working standard the o/p current will fall to 
<3.00mA which will be detected at the control unit has a sensor fault. 

Zero point Calibration: 

A manual zeroing of the sensor can be performed when the sensor has been powered for a minimum of 
one hour. The zero can be performed when the sensor is in a known fresh air, Non refrigerant gas 
environment or gassed with Nitrogen. The sensor must be in one of the three above conditions for a 
minimum of five minutes or until the output has reached a stable point. 
 
To perform a manual zero: 
1. Remove the GDA 3160 from the wall to access the back of the sensor unit; 
2. Add a jumper to pins 1 and 3 of 

P4

 see picture below, This enters Manual Calibration Mode (see table 

for LED sequence); 
3. Press and hold the ZERO calibration button 

SW1

 for one second (see table for LED sequence): 

 

If the zero was successful a short beep will be heard (see table for LED sequence) 

 

If the zero was 

not

 successful a two sec beep will be heard (see table for LED 

sequence). Repeat step 3 after ensuring that the sensor is in fresh air and stable.  

4. When successfully zeroed remove the Manual Calibration jumper from header

 P4

 and return to normal 

operation. 
 
 
 

Summary of Contents for GDA 3160

Page 1: ...GDA 3160 3100 V5 5 HARDWARE AND ABOVE Refrigerant Gas Detector Operating Manual Copyright Gas Detection Australia Pty Ltd Dec 2017...

Page 2: ...f cable run Screen must be connected to the Earth connection on the connector P1 Power Consumption 300mW average Output Types 4 20mA Standard 0 20mA 0 5v 0 10v User Specified Target Gas Refrigerant R2...

Page 3: ...he further from the potential leeks the more the gas will be diluted Take into account drafts and air movements when mounting the sensor IT IS VERY IMPORTANT THAT THE GDA 3160 IS INSTALLED IN THE MOST...

Page 4: ...rrying capability to suit the length of cable run Screen must be connected to the Earth connection on the connector P1 The Protection Cover Plate is used to protect the main PCB from most cases of sta...

Page 5: ...at this does not affect external equipment LED STATE FUNTION ON Power is present OFF Power is not present LEDs CHASE Sensor is in its initialisation period approx 30 secs but in some sensors this can...

Page 6: ...ve into a maximum of 680 load impedance line and input impedance at 24V Be cautious when handling the GDA 3160 as there are delicate components that can easily be damaged by static discharge Always ob...

Page 7: ...JP6 The alarm enable jumper has been factory set to on for ver 5 5 If the MUTE link Purple is in it will mute the on board buzzer If the optional mute button is installed the on board buzzer can be m...

Page 8: ...in service if the sensor falls below a minimum working standard the o p current will fall to 3 00mA which will be detected at the control unit has a sensor fault Zero point Calibration A manual zeroi...

Page 9: ...Zero 0 5 sec Alternate Blinking at once per second for 4 sec Zero Successful 0 1 sec Fast Blink for 2 sec Zero Failed Solid for 2 sec Manual Calibration Mode Add a jumper to pins 1 and 3 of P3 P4 LED...

Page 10: ...Gas Detection Australia Pty Ltd Page 10 of 12 M 3160 003 1 05 12 2017 Thank You For Supporting Australian Manufactured Products...

Page 11: ...Gas Detection Australia Pty Ltd Page 11 of 12 M 3160 003 1 05 12 2017 Notes...

Page 12: ...Gas Detection Australia Pty Ltd Page 12 of 12 M 3160 003 1 05 12 2017...

Reviews: