Installation:
The sensor is suitable for indoor use only. If it is going to be used in external environments seek specialist
advice from GDA.
Mount the sensor as close as possible to where the leak of the refrigerant gas being detecting may occur
as the distance from a potential leek effects the time taken to detect it. The further from the potential
leeks the more the gas will be diluted.
Take into account drafts and air movements when mounting the sensor.
IT IS VERY IMPORTANT THAT THE GDA 3160 IS INSTALLED IN THE MOST UPRIGHT POSITION AGAINST
VERTICAL STRUCTURE
DO NOT EXPOSE THE SENSOR FACE TO DIRECT WATER DROPLETS OR CONDENSING ATMOSPHERES
These sensors use critically aligned optical benches and should not be
subjected to vibration or mechanical shock. Handle with care.
GDA 3160 SENSOR INSTALLATION POSITION
___________________________________________________________________________________
YES
NO
NO