Gas Detection (Australia) Pty Ltd
Page 11 of 24
M-GDA-2400-16/01/2017 Rev 8
GDA 2400 Setup and Configuration
Most systems are factory set up with the sensors ordered and this section will not
have to be followed
The GDA 2400 can be configured via a menu system. The menu system is navigated using the buttons
on the GDA 2400 front panel or keyboard interface.
Most systems are factory set up with the sensors ordered and this section will not
have to be followed.
The GDA 4020 sensor inputs can be configured via a menu system. The menu system is navigated
using the four buttons on the GDA 4020 front panel or keyboard interface. The screen is divided into
4 lines. The bottom line relates to the button underneath the display, or if using a keypad, the
button position on the key pad.
The following parameters are programmable by the user:-
1.
Select
Chan 1
or
Chan 2
2.
Select if it is
ON
or
OFF
3.
Input
Location
name
4.
Input
Gas
name from list provided page 11.
5.
Input the
Units
of measurement (
ppm, %LEL, % VOL
)
6.
Select if the display is to show
Value
of gas level or
OK
whilst it is 20 % away from the alarm
level
7.
Input the sensor
Range
8.
Alarm level 1
in preselected units (ppm, %LEL, % VOL)
9.
Alarm level 2
in preselected units (ppm, %LEL, % VOL)
10.
Alarm level 3
in preselected units (ppm, %LEL, % VOL)
11.
Hysteresis
12.
Sign
Rising
or
Falling
13.
Alarm
Latched
or
unlatched
14.
Alarm delay
(seconds)
15.
Relay on time
(minutes )
ALL THE ABOVE IS REPEATED FOR BOTH CHANNELS IF BOTH SENSORS ARE ON