background image

LS4 MINI

Box 203, SE–335 25 Gnosjö
Phone: +46 (0) 370 33 28 00
[email protected]

garo.se

Manual 380285 1.0

Assembly instructions / End User Instructions (EN)

GARO AB

EN

Summary of Contents for LS4 MINI

Page 1: ...LS4 MINI Box 203 SE 335 25 Gnosjö Phone 46 0 370 33 28 00 info garo se garo se Manual 380285 1 0 Assembly instructions End User Instructions EN GARO AB EN ...

Page 2: ...ORMATION 3 Warnings 3 Cautions 4 Notes 4 Content 4 INSTALLATION 5 USER MANUAL 7 Normal use 7 LED indications 7 Dimensional sketch 11 Technical specifications 12 Service Maintenance 13 Service and maintenance form 13 Installation Form 14 2 EN ...

Page 3: ...ear flammable explosive harsh or combustible materials chemicals or vapors Turn off the electrical power at the circuit breaker before installing configuring cleaning or maintenance Use LS4 MINI only within the specified parameters Never spray water or any other liquid directly at LS4 MINI Never spray any liquid onto the charge handle or submerge the charge handle in liquid Store the charge handle...

Page 4: ... any questions please contact your local electrical authority Ensure that the charging cable is positioned so it will not be stepped on driven over tripped on or subjected to damage or stress Unroll the charging cable to prevent it from overheating Do not use cleaning solvents to clean any of the components The outside of the LS4 MINI the charging cable and the end of the charging cable should be ...

Page 5: ...fuse and cable information in the Installation form located in the installation manual that is included in the box 3 Mount the LS4 MINI on a wall or on a pedestal figure 1 6 Note Wall installation requires a minimum 20mm distance between the wall and the LS4 MINI to ensure correct cooling figure 4 Recommendation is to use the included wallbracket 4 Install the electric supply cable L1 L2 L3 and N ...

Page 6: ...ALLATION CU L1 L2 L3 N 6Nm PE 2 5 10mm 5Nm 16 50mm 10Nm AL L1 L2 L3 N 2 5 16mm 5Nm 25 50mm 10Nm PE 2 5 10mm 5Nm 16 50mm 10Nm Pedestal Accessory 0 8Nm 0 05 figure 4 figure 5 figure 3 4x ALU CU adapters 6 EN ...

Page 7: ...ng station detects that the cable is connected but is yet to detect the EV Blinking green 30 second blink Whenever during operation Charging station have received command from backend to start charging and is waiting for EV to connect Firm blue EV connected Charging is ongoing state C EV connected Charging is paused state B Blinking blue Whenever during operation Charging station point is reserved...

Page 8: ...is connected correctly Check the intake on the EV for obstructions dirt Firm blue No error Have you tried everything without success Contact Your retailer and as 2nd option contact Volvo Action Service please have M number available No error Blinking blue No error contact backend operator if this is not the desired mode Blinking yellow When RFID is presented Charging station is verifying the RFID ...

Page 9: ... current in backend charger configuration OperatorCurrentLimit Check motor locking wiring and connection for damages Verify that locking mechanism rod and arm are not stuck Verify that the connector is properly inserted into the socket Light force may be applied Verify that there are no foreign objects inside the socket inlet on the EV hence blocking the connector Check charging cable and connecto...

Page 10: ... unit delivers 12DC on the output terminals when red black cables were disconnected then it has detected an earth fault in one of the DC powered components controllers upper PCB router switch etc inside the charging station If LED light DC OK remains turned off consider replacing the 12V power supply unit Check red black cable and connection between DC terminal and upper PCB quick connection locat...

Page 11: ... AUTHORIZED available A Vehicle not connected Firm blue CHARGING occupied C Vehicle connected ready CHARGING suspendedEV B Vehicle connected not ready Blinking blue Reserved Firm red RCD triggered groundFailure Residual current detected via sensor groundFailure MCB of type 2 socket triggered overCurrentFailure Actuator unlocked while charging connectorLockFailure Plug locking failed on the EV side...

Page 12: ...arging type Mode 3 Charging method AC Charging Protection class IP44 Mechanical impact resistance IK10 Temperature range 25C 40C Weight 25kg Standard cable length 7 5m Rated current withstand 10kA Rated short time withstand current 10kA Rated conditional short circuit current of an assembly 10kA Rated impulse withstand voltage 4kV Rated insulation voltage 230 400V Rated current 63A Rated diversity...

Page 13: ...artners You can normally find information inside the LS4 MINI if it is connected to a supervised system Service and maintenance form Check point for annual maintenence Status Value Comment remark Visual check outside cabinet LED indication lit Check cables connectors connector pins Check color foil and instructions Check fastening fixing to ground wall Clean LS4 MINI outside surface Check both RCC...

Page 14: ...NUAL Installation Form LS4 MINI Model M nr ELECTRICAL INSTALLATION DATA Group fuse A Supply cable dimension FUNCTION TEST Testbox Date Sign Installer Company Name Owner Customer Name Installation address 14 EN ...

Page 15: ...GARO AB Box 203 SE 335 25 Gnosjö Phone 46 0 370 33 28 00 info garo se garo se EN ...